• HVHIPOT Turn to Turn Surge Insulation Strength Tester for 10kV Motor
  • HVHIPOT Turn to Turn Surge Insulation Strength Tester for 10kV Motor
  • HVHIPOT Turn to Turn Surge Insulation Strength Tester for 10kV Motor
  • HVHIPOT Turn to Turn Surge Insulation Strength Tester for 10kV Motor
  • HVHIPOT Turn to Turn Surge Insulation Strength Tester for 10kV Motor

HVHIPOT Turn to Turn Surge Insulation Strength Tester for 10kV Motor

Power Supply: 220V±5%
Frequency: 50Hz/60Hz ±2%
Peak voltage: 0-30kV
Trigger times: 6.25 time/s- 50 times/s
Waveform rising time: 0.1-0.5μS
Capacitance error: (+0.3)/(-0.1) µs
Customization:

360° Virtual Tour

Diamond Member Since 2011

Suppliers with verified business licenses

Manufacturer/Factory & Trading Company

Basic Info.

Model NO.
GDZJ-30S
Impulse capacitance
0.01μF -0.1μF
Max output energy
60J
Power consumption
1000VA
Transport Package
Wooden Case
Specification
ISO, SGS
Trademark
HV Hipot
Origin
Wuhan China
HS Code
9030332000
Production Capacity
2000PCS/Year

Product Description

HVHIPOT Turn to Turn Surge Insulation Strength Tester for 10kV Motor


GDZJ-30S Turn To Turn Surge Withstand Tester

Product Description

GDZJ-30S is used to test turn-to-turn insulation strength of rate voltage 10kV motor ,HV and LV motor ,AC/DC motor, transformer winding and coil winding. 


Features

 It can detect below faults:

  • Turn-to-turn Insulation breakdown
  • Coil-to-coil and winding -to-winding corona discharge
  • Winding connection mistake
  • Winding disconnection
  • Turn-to-turn difference
  • Short-circuit between interphase, winding phase or iron core

Specifications
 
Input voltage 220V±5%
Frequency 50Hz/60Hz ±2%
Measurement range 0-30kV,continuous adjustment,±5%
Trigger times 6.25 time/s- 50 times/s
Waveform rising time 0.1-0.5μS
Capacitance error (+0.3)/(-0.1) µs
Impulse capacitance 0.01μF -0.1μF
Max output energy 60J
Power consumption 1000VA
Insulation resistance insulation resistance between power input terminal and tester ≥20MΩ
Dielectric strength 1500V/50HZImin, there is no flashing and breakdown for withstand voltage test.
Temperature 0-40 degree
Relative humidity ≤80% at 40 degree
Waveform capacitance deviation ±3%
Dimension 650*550*1700mm
Weight 100kg
Application turn to turn withstand voltage test for rated voltage 10kV motor.