Gold Member Since 2011
Audited Supplier
HV Hipot Electric Co., Ltd.

Cable Fault Locator, Cable Fault Tester, Cable Fault System manufacturer / supplier in China, offering Cable fault locator for 16kV cable testing, Heat-Engine Plant Raw Material Management IOT System (GD-MIOT), Cable fault location set and so on.

(/ )

Supplier Homepage Product Cable Fault Locator Cable fault locator for 16kV cable testing

Cable fault locator for 16kV cable testing

FOB Price: Get Latest Price
Min. Order: 1 Piece
Port: Wuhan, China
Production Capacity: 500PCS/Year
Payment Terms: L/C, T/T, Western Union

Request a custom order and have something just for you!

Send Customized Request
Basic Info
  • Model NO.: GD-2138
  • Usage: Digital Cable Tester
  • Power: Electricity
  • Customized: Customized
  • Power Supply: AC220V and Built-in Chargeable Battery
  • Resolution: 1m
  • Impulse Voltage: 0-32kv Adjustable
  • Ambient Humidity: <80% Rh
  • Trademark: HV Hipot
  • Specification: ISO, SGS
  • HS Code: 9030899090
  • Test Mode: Point Test
  • Test Region: Hv Cables
  • Certification: SGS, ISO9001
  • Color: Gray
  • Fault Distance: Max. 32km
  • Fade Zone: 1m
  • Ambient Temperature: 0-40 Degree
  • Dimension: 750× 570× 1200mm
  • Transport Package: Wooden Case
  • Origin: Wuhan China
Product Description
The system includes:
GD-2138 Mainframe.
GD-2132R Receiver.
RF Inductive Tracking Rod.
Potential Difference Locating Rack with 2 pins.
AF Stethoscope and Headphones (for Listening mode).
Grounding Pin.

Cable fault locator for 16kV cable testing                        Cable fault locator for 16kV cable testing                      Cable fault locator for 16kV cable testing
GD-2138 Mainframe                             AF Stethoscope                                Headphone
 
Cable fault locator for 16kV cable testing             Cable fault locator for 16kV cable testing           Cable fault locator for 16kV cable testing
          GD-2132R                                        PD Locating Rack                     RF Tracking Rod


GD-2138 Cable Fault Locator System is movable cable fault detection device which is applicable for various types of power cable, communication cables. It can accurately measure the distance of cable fault and locate the fault point.

Features
Large LCD display, easy to operate.
Directly detect high resistance fault, without burning.
Display the direct or relative distance between testing and fault points.
Auto search along the wave for inflexion, easy to measure fault distance.
Waveform Comparison Method helps to detect puzzling fault.
Wave velocity of test cable can be calibrated.
Test data and wave can be saved, viewed and printed.

Specifications
Power supply: AC220V and Built-in Chargeable Battery
Fault Distance: Max. 32km
Resolution: 1m
Fade Zone: 1m
Impulse Voltage: 0~35kV adjustable
Ambient Temperature: 0~40oC
Ambient Humidity: <80% RH
Dimension: 750× 570× 1200mm
Weight: 120kg.

GD-2138 Mainframe
GD-2138 is the main body of cablefault locator, it can measure the distance of cablefault, trace the test cable, and locate the fault point.

Features
High Measuring Accuracy, 1m Resolution.
Large LCD and Menu and function buttons, easy to operate.
Directly detect high impedance cablefault without burning.
Display the direct or relative distance between testing and fault points.
Auto search along the wave for inflexion, easy to measure fault distance.
Waveform Comparison Method helps to detect puzzling fault.
Wave velocity of test cable can be calibrated.
Test data and wave can be Saved, Viewed and Printed.

Specifications
Power supply: AC220V and Built-in Chargeable Battery
Fault Distance: Max. 32km
Resolution: 1m
Fade Zone: 1m
Impulse Voltage: 0~35kV adjustable
Ambient Temperature: 0~40oC
Ambient Humidity: <80% RH
Dimension: 750*570*1200mm
Weight: 120kg

GD-2132R Receiver
GD-2132R receives the signals from RF Inductive Tracking Rod and Potential Difference Locating Rack, and AF Stethoscope. It is used to trace cable and locate cablefault. It uses RF electromagnetic induction method to probe the cable track and deepness, uses potential difference method or AF stethoscopy method to locate the fault point. It is applicable to the cables with metal.

Features
High Receive Sensitivity
Low Static Drift
High Accuracy and Reliability
Great Anti-interference's ability
LCD screen
AC/DC Power Source

Specifications
Max. Distance to trace and locate: 20km, or 3km if Φ < 0.5;
Impedance Range of fault point to locate: 0~50M ohm;
Locating Accuracy: <+-10cm;
Probe Deepness: <3m;
 