Gold Member Since 2011
Audited Supplier
HV Hipot Electric Co., Ltd.

Ac Resonance Test Systems, Hv Cable Ac Resonance Test Systems, Cable Ac Resonance Test manufacturer / supplier in China, offering Cable AC Resonance Test Systems (GDTF-HVC), Resistive High Voltage Divider GDFR-R Series, GDYD-A Automatic AC High Voltage Test Set (<5kVA) and so on.

(/ )

Supplier Homepage Product HV Resonant Test System Cable AC Resonance Test Systems (GDTF-HVC)

Cable AC Resonance Test Systems (GDTF-HVC)

FOB Price: Get Latest Price
Min. Order: 1 Piece
Production Capacity: 1000PCS/Year
Transport Package: Wooden Case
Payment Terms: L/C, T/T, Western Union

Request a custom order and have something just for you!

Send Customized Request
Basic Info
  • Model NO.: GDTF-HVC
  • Customized: Customized
  • Rated Output Voltage: 0 ~ 66kv(Effective Value) and The Below. (Customiz
  • Resonant Voltage Waveform: Sine Wave, Thd <= 1%
  • Trademark: HV Hipot
  • Origin: Wuhan China
  • Certification: SGS
  • Power Supply: 220V or 380V Single-Phase
  • Output Frequency: 20-300Hz
  • System Quality Factor: Maximum Load >= 20
  • Specification: ISO, SGS
  • HS Code: 9030339000
Product Description
GDTF series Cable AC Resonance Test Systems are composed of frequency/voltage adjustment power, excitation transformers, reactors, capacitor divider. It adopts mode of power frequency adjustment to make reactor and tested capacitor realize resonance.

Features
1. Small size, light weight, portable design;
2. Single parts not more than 30kg, easy to carry;
3. Power supply with 220V or 380V single-phase, convenient for on-site power sourcing;
4. Dry type epoxy cast for reactor, nice and reliable, suitable for various types of cables;
5. Imported SPWM digital waveform generated chip. 16 digit frequency resolution. Frequency fineness up to 0.1Hz at frequency of 20-300Hz;
6. Advanced IPM module, ensure stability and security of apparatus.

Technical parameters
Rated output voltage: 0 ~ 66kV(effective value) and the below. (customized, according to test object)
Output frequency: 20-300Hz.
Resonant voltage waveform: Sine wave, THD <= 1%.
Full load working time: Continuous working time 60mins.
System quality factor: Maximum load >= 20.
Frequency adjustment: Fineness 0.1Hz, instability <=0.01%.
Power supply: 220V or 380V single-phase.