• HVHIPOT Single Phase Relay Protection Tester GDJB-II
  • HVHIPOT Single Phase Relay Protection Tester GDJB-II
  • HVHIPOT Single Phase Relay Protection Tester GDJB-II
  • HVHIPOT Single Phase Relay Protection Tester GDJB-II
  • HVHIPOT Single Phase Relay Protection Tester GDJB-II
  • HVHIPOT Single Phase Relay Protection Tester GDJB-II

HVHIPOT Single Phase Relay Protection Tester GDJB-II

After-sales Service: yes
Warranty: 1 year
Type: Universal Testing Machine
Accuracy Grade: 1
Load Way: Electronic Load
Loading Method: Dynamic Load
Customization:

360° Virtual Tour

Diamond Member Since 2011

Suppliers with verified business licenses

Manufacturer/Factory & Trading Company

Basic Info.

Model NO.
GDJB-II
Display
Digital
Control
Computer Control
Weight
0-100Kg
Power Source
AC220V
Power Supply
AC 220V+/-10%, 50Hz
Working Environment
Temperature -10--40centigrade
Humidity
<=85%
Atmosphere
86-106kpa
Output Power Supply
AC Voltage: 0-220V/3A
AC Current
0-100A/7.5V
Transport Package
Carton or Wooden Case
Specification
ISO, SGS
Trademark
HV Hipot
Origin
China
HS Code
9030820000
Production Capacity
2000PCS/Year

Product Description

Single Phase Relay Protection Tester GDJB-II

Product Description

GDJB-II relay protection calibrator is a new generation of calibration device developed by our company. The AC/DC voltage and current source inside the instrument adopts the latest power supply technology, which makes the instrument reach the domestic advanced level in circuit design, device selection, panel layout and internal structure design. The instrument has the advantages of perfect functions, excellent material selection, clear test project data, simple operation, etc. It is the preferred equipment for the power conservation department.


1. Measuring relay: It can measure the starting value, return value and return coefficient of current and voltage relay.
2. Time relay: It can measure the starting value, return value and its action time.
3. Intermediate relay: It can measure the starting value, return value, holding value and operating time of various intermediate relays with starting coil and holding coil.
4. Reclosing relay: Capacitor charging test, charging time, reclosing time and intermediate component test.
5. Differential relay: DC excitation test, braking characteristic test, volt-ampere characteristic test.

Features

A. Working conditions

Power supply: AC 220V+/-10%, 50Hz
Working environment: Temperature -10--40centigrade
Humidity: <=85%
Atmosphere: 86-106kPa
 
B. Output power supply
 

AC voltage

0-220V/3A

AC current

0-100A/7.5V (200A can be customized)

0-20A/25V

0-5A/5V

DC voltage

0-220V/3A

DC current

0-20A/25V

Fixed voltage output

DC 24V/48V/110V/220V

 
C. Performance Index
Ammeter and voltmeter: 4 1/2 digit.
Digital millisecond meter: 0-99.9999s
 
D. Functions
 
1. Measure relay: Measure start value, return value and drop-off to pick-up ratio of current, voltage relay.
2. Time relay: Measure start value, return value and action time.
3. Intermediate relay: Measure all kinds of coil with start. Remain start value, return value, holding value and action time of coil intermediate relay.
4. Reclosing relay: Charge test of capacitance, charge time, reclosing time and middle components test.
5. Differential relay: DC Excitation test, Braking test, Volt-ampere characteristic test.
6. Other unconventional relays and LV circuit breakers.
 
HVHIPOT Single Phase Relay Protection Tester GDJB-II
HVHIPOT Single Phase Relay Protection Tester GDJB-II
HVHIPOT Single Phase Relay Protection Tester GDJB-II
HVHIPOT Single Phase Relay Protection Tester GDJB-II

 

Send your message to this supplier

*From:
*To:
*Message:

Enter between 20 to 4,000 characters.

This is not what you are looking for? Post a Sourcing Request Now