• HVHIPOT AC Hipot Test Set 10kVA/100kVAC (100kVAC 100mA) GDYD-1010D
  • HVHIPOT AC Hipot Test Set 10kVA/100kVAC (100kVAC 100mA) GDYD-1010D
  • HVHIPOT AC Hipot Test Set 10kVA/100kVAC (100kVAC 100mA) GDYD-1010D

HVHIPOT AC Hipot Test Set 10kVA/100kVAC (100kVAC 100mA) GDYD-1010D

After-sales Service: YES
Warranty: 1
Type: Withstand Voltage Test Set
Load Way: Electronic Load
Loading Method: Dynamic Load
Display: Digital
Customization:

360° Virtual Tour

Diamond Member Since 2011

Suppliers with verified business licenses

Manufacturer/Factory & Trading Company

Basic Info.

Model NO.
GDYD-1010D
Control
Manual Control
Power Source
AC220V
Power Supply
AC220V±10%, 50Hz
Capacity
10kVA (based on selectable)
HV Source
Epoxy resin cast HT transformer(Dry type testing t
Output control
Manual control
Metering
Digital display, kV meter: AC 0-100kV, mA meter: A
Transport Package
Wooden Case
Specification
ISO, SGS
Trademark
HV Hipot
Origin
Wuhan China
HS Code
9030332000
Production Capacity
2000PCS/Year

Product Description

HVHIPOT AC Hipot Test Set 10kVA/100kVAC (100kVAC 100mA) GDYD-1010D

I. General information


AC hi-pot testing is the effective and direct way to test insulation strength for electrical equipments, apparatus or machines. It checks dangerous flaws which assure electrical equipment continuous working.

Typical applications include testing of transformers, switchgear, cables, capacitors, aerial motors platforms, hot sticks bucket bricks, vacuum bottles and other related equipment like vacuum interrupters, blankets, ropes, gloves, hydraulics hose, instruments transformers generators.

II. Features

Digital display panel mounted controls & indicators with easy to read legend.

Monitoring high voltage side voltage,low voltage side current and indicator of zero, power, working start,timing.
Over-current protection, zero-starting protection, sound and light alarm.
Continuously variable output from zero to full voltage.
Adjustable over current protection,with trip levels variable from 10 to 110%.
With new type time relay, time range is more wider (1S ~ 99H).
Using the latest current relay, more accurate and reliable.
Light weight, small size, easy to move.


III. Specifications
 
Input AC220V ± 10%
Frequency 50Hz ± 1
Output 0-100kV,  AC RMS
Rating 100%Rated-1minute, 50%-continuous
Capacity 10kVA (based on selectable)
HV Source Epoxy resin cast HT transformer(Dry type testing transformer)
Output control Manual control
Voltage accuracy ≤ 1.0% (F.S)
Current Accuracy ≤ 1.0% (F.S)
Timing range  0-99H
Metering Digital display, kV meter: AC 0-100kV, mA meter: AC 0-100mA
Humidity 85% RH
Environmental temperature -20ºC~50ºC
Weight Control Unit:About 40kg
Dry Type Testing transformer:About 75kg.