Suppliers with verified business licenses
AC Current Output | Phase current output (RMS) 0~40A Maximum parallel current output (RMS) 0~120A Long-term allowable working value of phase current (RMS) 10A Maximum output power of phase current 420VA Maximum output power of 3-phase parallel current 900VA Allowable working time of maximum 3-phase parallel current 10s Frequency range(Fundamental wave) 20~1000Hz Harmonic 1~20 times Accuracy <±0.2% |
DC Current Output | Current output 0~±10A/phase, 0~±30A/3-phase parallel Maximum output load voltage 20V Accuracy <±0.2% |
AC Voltage Output | Phase voltage output (RMS) 0~120V Line voltage output (RMS) 0~240V Phase/line voltage output power 80VA/100VA Frequency range(Fundamental wave) 20~1000Hz Harmonic 1~20 times Accuracy <±0.2% |
DC Voltage Output | Phase voltage output amplitude 0~±160V Line voltage output amplitude 0~±320V Phase/line voltage output power 70VA/140VA Accuracy <±0.2% |
Binary Input | 8-way Idle contact 1~20mA, 24V Electric potential contact "0": 0~+6V; "1": +11 V~+250V |
Binary Output | 4 pairs DC: 220V/0.2A; AC: 220V/0.5A |
Time Measurement | Measuring range 0.1ms to 9999s; accuracy: 0.1ms |
Power Supply | AC220V±10%, 50/60Hz |
Ambient Temperature | -10ºC~50ºC |
Dimension | 410×360×200mm |
Weight | 20kg |
Rated output | Frequency error <±0.01Hz Phase error <±0. 2° Waveform distortion <±0.3% (fundamental wave) Time error <40µs Output frequency 0~1050Hz GDJB posed harmonic wave 0-21times |
Power voltage | Allowable range AC220V±10%, 50Hz±10% |
Ambient temperature | Use range 0~45ºC Storage range -25~70ºC |
Time measurement | Test range 0.1ms~999999.999s |
Exterior appearance of cabinet | Electromagnetic compatible cabinet, which is made of high-grade all aluminum alloy extruded section and has fine appearance, is selected. Dimension of cabinet: length×width×height 360mm ×195mm ×375mm |
Weight of cabinet | Weight of host machine 16.6kg |
Load-bearing output | Selectable between light load or heavy load output (When any phase current output surpasses 15A, it is suggested to press key F3 before test of each functional module so as to switch to heavy load output mode) |
Suppliers with verified business licenses