• HVHIPOT high voltage Partial Discharge Test System for cable, PT
  • HVHIPOT high voltage Partial Discharge Test System for cable, PT
  • HVHIPOT high voltage Partial Discharge Test System for cable, PT
  • HVHIPOT high voltage Partial Discharge Test System for cable, PT

HVHIPOT high voltage Partial Discharge Test System for cable, PT

Rated Capacity: 10kVA
Output Voltage: 100kv
Output Current: 100mA
Input Voltage: 200V
Input Current: 50A
Short-Circuit Impedance: ≤ 8%
Customization:

360° Virtual Tour

Diamond Member Since 2011

Suppliers with verified business licenses

Manufacturer/Factory & Trading Company

Basic Info.

Model NO.
GDYT-10kVA/100kV
Transport Package
Wooden Case
Specification
ISO, SGS
Trademark
HV Hipot
Origin
Wuhan China
HS Code
9030899090
Production Capacity
2000PCS/Year

Product Description

HVHIPOT high voltage Partial Discharge Test System for cable, PT

General introduction

It is mainly used for testing frequency voltage insulation level of various insulation materials, insulation structure and electrical products, also as partial discharge frequency testing power supply for testing object such as transformer, mutual inductor and lightning arresters. It widely used in electrical manufacturing, power operation departments, research institutes and universities.

GDYT System 10kVA/100kV composition
Name Function
Hipot Test Control Table GDYD-10/100  Controlling and voltage boosting for test object which boosted to the rated voltage.
PD-free Gas type transformer YDQW-10/100   
Coupling capacitor  TAWF-600pF/100kV   Transmitting partial discharge signal to partial discharge detector.
Protective resistor GR100kV  
Isolation filter LBQ-10kVA Device of anti-interference caused by power supply.
Partial discharge detector GDJF-2008 Detecting and displaying partial discharge capacity.
Other accessories  


Features

1. 320*240 LCD screen,high speed thermal printer.
2. HV voltage,HV current,LV voltage,LV current measuring mode,High-precision sensor and high performance 14digit AD acquisition chip.
3. Real-time show HV voltage,HV current,LV voltage,LV current,time and withstand result.
4. Zero-returning detection.When it it back to zero,the test can be started.
5. Insulation resistance detection function,show insulation strength of test object directly.
6. Advanced PD-free epoxy insulating sleeve, small partial discharge capacity.
7. Low impedance voltage.
8. Automatic control technology, good anti-interference performance.
9. Rapid electronic protection, high reliability.


System Specifications
 
Power supply 220V±22V,50HZ
Rated Capacity 10kVA  
Output Voltage:           100kV, current: 100mA
Input Voltage: 200V, current: 50A
short-circuit impedance: ≤ 8%
Operation time 60mins@100% rated voltage and current.
Continuous working@ 50% rated voltage and current.
Wave form distortion rate:<5% when voltage regulator input voltage distortion rate <3%, within 10-100% rated voltage range.
PD value ≤8pC @ 100% rated voltage
≤5pC @ 80% rated voltage

Send your message to this supplier

*From:
*To:
*Message:

Enter between 20 to 4,000 characters.

This is not what you are looking for? Post a Sourcing Request Now