| IEC 255-8: 1990 | Electric Relays Part 8: Thermal Electrical Relays |
| DL/T 624-2010 | Technical Specification of Test Equipment Based on Micro-computer for Relaying Protection |
| DL/T 846-2004 | General Technical Specifications for High Voltage Test Equipments |
| DL/T 596-2005 | Preventive Test Code for Electric Power Equipment |
|
GB50150-2016
|
Electrical Equipment Installation Engineering-standard for Hand-over Test of Electric Equipment |
|
IEC 60529:2013
|
Degrees of Protection Provided by Enclosure (IP Code) |
|
GB2900
|
Electro-technical terminology |
|
IEC60060-1,2
|
High Voltage Test Techniques |
|
IEC60071
|
Insulation co-ordination for High Voltage Transmission and Distribution Equipment |
1.3.1 Power Supply Voltage: 380V±10% 50HZ±1% Waveform Distortion Rate ≤5%
1.3.2 Ambient Temperature: -5ºC-40ºC
1.3.3 Ambient Humidity: ≤80%RH, no condensation, no instrument flickering
1.3.4 Altitude: ≤1000m
1.3.5 The operating environment should be free from obvious dust, smoke, corrosive, flammable gases, water vapor, and salt spray, and free from severe vibration.
2.1 Power Input: 380V±10%, 50HZ±1%, Three-phase four-wire system
2.2 Rated Power: 3*1KVA
2.3 Output Open Voltage: 2V
2.4 Current Output: 3*500A or 3*50A
2.5 Output Accuracy: 0.5 grade
2.6 Output Current Mode: True RMS continuously adjustable;
2.7 Output Waveform: Standard sine wave;
2.8 Output Voltage: 380V, 220V
2.9 Current Stability: 0.2%;
2.10 Current Waveform Distortion: THD 1%;
2.11 Measurement Range: 0.1ms---9999.9s, Accuracy: 0.1ms
2.12 Ripple Coefficient: <0.3%
2.13 Dimensions: 580*400*400mm, 50KG