Plastic box 50kV AC DC Hipot Test Set for Transformer
I. General information
GDYD series AC/DC hipot testing is the effective and direct way to test insulation strength for electrical equipments,apparatus or machines. It checks dangerous flaws which assure electrical equipment continuous working.
Typical applications include testing of transformers, switchgear, cables, capacitors, aerial motors platforms, hot sticks bucket bricks, vacuum bottles and other related equipment like vacuum interrupters, blankets, ropes, gloves, hydraulics hose, instruments transformers generators.
II. Features
- Digital display meters mounted on the panel.
- Monitoring HV side voltage, HV side current, LV side current and indicator of zero, power, working start, timing.
- Over-current protection, zero-starting protection, sound and light alarm.
- With new type time relay, time range is more wider (1S ~ 99H).
- Using the latest current relay, more accurate and reliable.
- Light weight, small size, easy to move.
III. Specifications
- Control unit specifications
- Power: AC220V, 50Hz
- Capacity: 5kVA
- Output voltage: AC 0-250V
- Rated output current: 25A
- Rated current rectified range: 0-25A
- HV voltmeter range: 0-50kV
Accuracy: 3% of the reading±1digit(F.S)
7. HV ammeter range: 0-100mA
Accuracy: 3% of the reading±1 digit(F.S)
8. LV ammeter range: 0-25A
Accuracy: 2.0% of the reading±1 digit(F.S)
9. Timing range:1s-99h
10. Weight: 19kg
11. Dimension: 440mm (L)*340mm (W)*240mm (H)
B. Testing transformer (HV unit) specifications
- LV side voltage (Input voltage): 0-200V
- LV side current (Input current): AC 0-25A
- HV side voltage(Output voltage): AC 0-50kV, DC 0-70kV
- HV side current(Output current): AC 100mA, DC71.4mA
- Capacity: 5kVA
- HV side/LV side turns ratio: 250:1
- Measuring voltage: AC 0-200V
Accuracy: 1.0% of the reading±1 digit(F.S)
8. No-load current: <10%
9. Impedance voltage: <10%
10. Weight: 45kg
11. Dimension: 450mm(L)*330mm(W)*1080mm(H)
C. Working conditions
- Working place: No gas, steam, chemical dust and explosive and corrosive medium which will influence insulation.
- Environment temperature: -20--50ºC
- Environment humidity: ≤85% RH (no condensing)
We can customize different ratings based on different requirement.Welcome to consult with us!