| Customization: | Available |
|---|---|
| Voltage: | 220V 110V 48V (optional 24V) or customize |
| Capacitance range: | System to the earth, total capacitance ≤100UF |
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
| Use Environment | |
| Ambient temperature | -30 ° C ~ +50 ° C; |
| Relative humidity | ≤95%; |
| Wireless communication technical indicators | |
| Signal power | ≤ 10dbm; |
| Signal band | 433Mhz; |
| Sensitivity | -106dBm; |
| Transmission distance | in the case of line-of-sight, reliable transmission distance of 250 meters from the ground 2 meters |
| Analyzer technical indicators | |
| Applicable DC system voltage level | 24V (customized), 48V, 110V, 220V or user-specified voltage level |
| System positive and negative voltage measurement range | 0-300V |
| DC voltage measurement range to ground | 0-300V |
| AC series power failure alarm threshold | 5V |
| Voltage measurement resolution | 0.1V |
| System ground resistance measurement range | 0-999.9KΩ |
| Grounding resistance measurement resolution | 0.1KΩ |
| Display mode | LCD |
| Detection signal current size | 0-2mA adjustable |
| Detection signal voltage amplitude | 0-50V adjustable |
| Signal frequency | no signal mode and 0.16Hz optional |
| DC-resistant system distributed capacitance interference | 1000uF |
| Detector technical indicators | |
| Insulation resistance detection range of branch circuit in signal mode | |
| System voltage rating is 220V | 0 -600KΩ |
| System voltage rating is 110V | 0 -300KΩ |
| System voltage rating is 48V | 0 -60KΩ |
| System voltage rating is 24V | 0 -20KΩ |
| Insulation resistance measurement resolution | 0.1KΩ |
| Insulation resistance detection range of branch circuit in no signal mode | |
| System voltage rating is 220V | 0 -50KΩ |
| System voltage rating is 110V | 0 -25KΩ |
| System voltage rating is 48V | 0 -10KΩ |
| System voltage rating is 24V | 0 -5KΩ |
| Insulation resistance measurement resolution | 0.1KΩ |
| Waveform display time | 12 seconds |
| Current measurement range | ±100mA |
| Current measurement resolution | 0.01mA |
| Display mode | LCD |
| Direction display mode | same or opposite direction |
| Anti-DC system branch distribution capacitance interference | 100uF |
| Distance to use with the analyzer | no distance limit |
| Jaw size | Diameter 30mm |