GDTF-HTS AC Resonant Test System for Substation Equipment
Product Details
| Customization: | Available |
|---|---|
| Rated Output Voltage: | 0 ~ 800kv (AC ) and Below |
| Output Frequency: | 20 ~ 300Hz |
Diamond Member Since 2011
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
Year of Establishment
2006-11-08
Number of Employees
68
Find Similar Products
Basic Info.
- Model NO.
- GDTF-HTS
- Waveform: Pure Sine Wave
- Thd <1.0%
- The Maximum Test Capacity
- 1000kVA and Below
- Duty Cycle: Full Power Output
- a Continuous Working Time 15min
- Quality Factor
- 30 ~ 90
- Frequency Adjustment Sensitivity
- 0.1Hz, Instability of <0.05%
- Transport Package
- Carton or Wooden Case
- Specification
- ISO, SGS
- Trademark
- HV Hipot
- Origin
- Wuhan China
- HS Code
- 9030339000
- Production Capacity
- 2000PCS/Year
Product Description

General introduction
Substation Electrical Apparatus AC Resonant Test Systems is mainly composed of frequency conversion control power, incentives transformers, reactors, capacitor divider, designed for substation electric equipment AC withstand voltage test of the voltage with 220KV or below. It satisfy capactive equipment AC withstand voltage test of transformer, GIS systems, SF6 switches, cables, casing.
This Series can meet high voltage, low current device test conditions requirement, also meet low voltage, high current device test conditions requirement, with a wide scope of application, is ideal test equipment for power department, repair engineering units and high voltage testing deparment.
Features
1. Smaller size, lighter weight compared with same voltage level, same capacity reactor.
2. Small temperature rise at rated load. Dry type epoxy cast, high mechanical strength, good insulation, nice and reliable.
3. Large capacity margin for frequency control source. Strong protection, good stability. with multiple working mode, easy to operate.
4. with 220V or 380V single phase power, convenient for onsite power sourcing.
5. Flexible configuration. Different type reactors for optional, can meet different test object requirements. Multifunctional, cost effective.
6. Imported SPWM digital waveform generated chip. 16 digit frequency resolution. Frequency fineness up to 0.1Hz at frequency of 20-300Hz.
7. Orthogonal non-synchronous fix type carrier modulation mode, ensure good output waveform for the entire frequency range.
8. Advanced IPM module, ensure stability and security of apparatus.
Technical Parameters
Rated output voltage: 0 ~ 800kV (AC ) and below;
Output frequency: 20 ~ 300Hz;
Waveform: Pure sine wave, THD <1.0%;
The maximum test capacity: 1000kVA and below;
Duty Cycle: Full power output, a continuous working time 15min;
Quality factor: 30 ~ 90;
Frequency adjustment sensitivity: 0.1Hz, instability of <0.05%;
Power Supply: 380/220V+/-15% / 50Hz+/-5%;
Product Configuration
| GDTF-108/108 | |
| Input voltage (V) | 380 |
| Output voltage (kV) | 0-108 |
| Capacity (kVA) | 108 |
| Application scope | 31500kVA or below |
| 35kV power transformer | |
| 35kV circuit breaker and bus bar,insulators | |
| 10kV (300 mm²) cable 2000m | |
| 35k V(300 mm²)cable 500m | |
| Main configurations | 5kW Variable frequency source 1 set |
| 5kVA Exciting transformer 1 set | |
| Reactors 27kV/1A 4sets | |
| Capacitive divider 100kV | |
| GDTF-216/216 | |
| Input voltage (V) | 380 |
| Output voltage (kV) | 0-216 |
| Capacity (kVA) | 216 |
| Application scope | 110kV Circuit breaker and bus bar |
| 110kV GIS | |
| 35kV(300 mm²) cable 1500m | |
| 10kV(300 mm²) cable 3km | |
| 110kV full insulation Transformer | |
| Main configurations | 10kW Variable frequency source 1 set |
| 10kVA Exciting transformer 1 set | |
| Reactors 54kV/1A 4sets | |
| Capacitive divider 200kV | |
| GDTF-270/270 | |
| Input voltage (V) | 380 |
| Output voltage (kV) | 0-270 |
| Capacity (kVA) | 270 |
| Application scope | 110kV GIS and transformer |
| 110kV GIS and transformer | |
| 35kV (300 mm²) cable 2km | |
| Main configurations | 15kW Variable frequency source 1 set |
| 15kVA Exciting transformer 1 set | |
| Reactors 54kV/1A 5sets | |
| Capacitive divider 300kV | |
| GDTF-200/400 | |
| Input voltage (V) | 380 |
| Output voltage (kV) | 0-400 |
| Capacity (kVA) | 200 |
| Application scope | 220kV GIS and transformer |
| 110kV GIS and transformer | |
| Main configurations | 10kW Variable frequency source 1 set |
| 10kVA Exciting transformer 1 set | |
| Reactors 100kV/0.5A 4sets |
|
| Capacitive divider 400kV | |
| GDTF-400/400 | |
| Input voltage (V) | 380 |
| Output voltage (kV) | 0-400 |
| Capacity (kVA) | 400 |
| Application scope | 220kV GIS and transformer |
| 10kV (300 mm²) cable 4km | |
| 35kV (300 mm²) cable 1km | |
| Main configurations | 20kW Variable frequency source 1 set |
| 20kVA Exciting transformer 1 set | |
| Reactor 100kV/ 1 A 4sets |
|
| Capacitive divider 400kV | |
| GDTF-520/260 | |
| Input voltage (V) | 380 |
| Output voltage (kV) | 0-260 |
| Capacity (kVA) | 520 |
| Application scope | 110KV Circuit breaker and bus bar |
| 110kV GIS | |
| 110kV (300 mm²) cable 800m | |
| 35kv (300 mm²) cable 3km | |
| 10kV (300 mm²) cable 6km | |
| 110kv full insulation Transformer | |
| Main configurations | 25kW Variable frequency source 1 set |
| 25kVA Exciting transformer 1 set | |
| Reactor 65kV/2A 4sets | |
| Capacitive divider 300kV | |
| GDTF-500/500 | |
| Input voltage (V) | 380 |
| Output voltage (kV) | 0-500 |
| Capacity (kVA) | 500 |
| Application scope | 220kV or below CT/PT |
| 220kV or below bushing | |
| 220kV or below Insulators, disconnectors | |
| 220kV or below Circuit breaker | |
| 220kV or below Insulation Instrument | |
| Main configurations | 20kW Variable frequency source 1 set |
| 20kVA Exciting transformer 1 set | |
| Reactor 125kV/1A 4sets | |
| Capacitive divider 500kV | |
| GDTF-600/600 | |
| Input voltage (V) | 380 |
| Output voltage (kV) | 0-600 |
| Capacity (kVA) | 600 |
| Application scope | 110kV (300 mm²) cable 800m |
| 35kv (300 mm²) cable 110m | |
| 35-220kV GIS ,transformers, insulators | |
| Main configurations | 30kW Variable frequency source 1 set |
| 30kVA Exciting transformer 1 set | |
| Reactor 120kV/1A 5sets | |
| Capacitive divider 600kV | |
| GDTF-800/800 | |
| Input voltage (V) | 380 |
| Output voltage (kV) | 0-800 |
| Capacity (kVA) | 800 |
| Application scope | 110kV (300 mm²) cable 800m |
| 220kv (300 mm²) cable 500m | |
| 35-500kV GIS ,transformers,insulators | |
| Main configurations | 40kW Variable frequency source 1 set |
| 40kVA Exciting transformer 1 set | |
| Reactor 200kV/1A 4sets | |
| Capacitive divider 800kV | |