HV HIPOT Primary current injection test sets high voltage electrical test equipment
I. General Information
GDSL-BX-100 Primary Current Injection Test Set, is mainly used for testing current transformer, motor protector, air switch, switch cabinet, circuit breaker, protection screen and etc.
II. Features
- PVC panel, simple and neat.
- With low power, big capacity autotransformer regulator and converter inside.
- Zero start function to prevent the test objects from damage caused by high current impulse. The equipment only can be started from zero.
- Impulse selection function. The required current can be output directly without zero protection function when making quick-break testing for circuit breaker.
- Accurate measurement. LCD digital indicator to display output current and voltage. The resolution of output current is 1A and output voltage is 1V.
- Portable design, suitable for on-site testing.
- Damping design, to ensure reliable transportation.
- The current range can be switched, easy to read.
- Engineering plastics box, dust-proof and waterproof, IP67 class.
- With wedge-shape air flue to improve heat-dissipation ability.
- Directly display primary current and secondary current, convenient for CT/PT turn ratios calibration test. (Optional)
III. Specifications
Power supply |
AC 220V 50Hz. |
Output power |
3kVA |
Output current |
500A in series,
1000A in parallel. |
Output voltage |
6V in series, 3V in parallel. |
Current can be adjusted smoothly and continuously. The accuracy is 1.0%. |
Output current is standard sine wave, waveform distortion is less than 5%. |
Output current |
RMS continuous adjustable. |
Duty Cycle |
5mins ON, 10mins OFF. |