I. General Information
The PD-free withstand voltage test device is the most rigorous, effective and direct method to identify the insulation strength of power equipment. It can detect those concentrated defects with greater dangers, which plays a decisive role in judging whether the power equipment can continue to participate in operation. It is an important means to ensure the insulation level of the equipment and avoid insulation accidents.
This device is an advanced withstand voltage test equipment designed according to the latest national power industry standards. It is used to conduct insulation strength tests on various electrical products, electrical components, insulating materials, etc. under specified voltages to assess the insulation level of the products, discover insulation defects in the tested products, and measure overvoltage capabilities.
II. Features
- Operation source configuration monitoring function: High voltage, low voltage current, timing indication.
- Protection function:over-current protection, over-load protection, over-heat alarm reminder.
- Adopt new time relay, wider timing range.
- The high-voltage coil of the test transformer is a cylindrical multi-layer tower, wound with high-quality polyester enameled wire and high-voltage insulation material.
- Test transformers (above 5kVA) are equipped with movable iron wheels.
- The device has wide practicality and covers high voltage partial discharge test of power supply in 45-400HZ frequency band.
System configuration
PD-free Variable Frequency Power Supply GDWB-10kW
PD-free Gas Transformer YDQW-10kW/100kV
Protective Resistor GR-100kV
PD-free Coupling Capacitor TAWF-100kV/100pF
Compensation Inductance GDDC-800V/20A
Isolation Boost Filter GDLB-10kVA/400V/800V
Digital Partial Discharge Detector GDJF-2008
III. Specifications
1.PD free Variable Frequency Power Supply GDWB-10kW
- Capacity: 10kW
- Power supply: Single phase AC220V±10% ,50Hz
- Frequency:45~400Hz
- Output voltage: AC 0-400V,1.0%FS±1dig
- Load regulation rate: 0.5
- Meter voltage:0-100V AC (Only used for step-up transformer instrument end to display high voltage)
- Partial discharge: <5pC
- PD-free Gas Transformer YDQW-10kVA/100kV
- Capacity:10kW
- LV voltage:400V
- LV current:25A
- HV voltage:100kV
- HV current:100mA
- Meter voltage:100V
- Ratio: High/Low = 1000:1
- Partial discharge: <5pC
3.PD-free Coupling Capacitor TAWF-100kV/100pF
- Rated voltage: 100kV
- Capacity: 100PF
- Measurement accuracy: <±1%
- Dielectric loss: <0.2%
4.Compensation Inductance GDDC-800V/20A
- Voltage:800V
- Current:20A
- Inductance:20mH
- Partial discharge:<5pC
Note: The amount of partial discharge in the on-site test system depends on the power supply, grounding and space interference (whether there is a shielded room).