General Information
HV-OWS-63 Oscillating Wave Test System (OWTS) for On-site PD Diagnostics of 10kV Cables is an integrated partial discharge location and management system. Test frequency varies from 50Hz to hundreds of Hertz under damping AC voltage.
It simulates the running state of the cable by applying voltage, and can induce partial discharge and detect its intensity and location. It uses a hollow inductor in series with the tested cable, and charges its series circuit through a high-voltage DC source. When the charging voltage reaches a preset value, it closes the electronic switches connected in parallel at both ends of the power source, thereby forming a damping oscillation circuit, generating an oscillating voltage, and this oscillating voltage is used to excite the partial discharge at the insulation defect of the cable, and the quality of the cable insulation can be judged by detecting the partial discharge.
Features
HV-OWS series is an integrated partial discharge test system, mainly used for partial discharge diagnosis of medium voltage cables. The system test frequency is 50Hz to several hundreds of Hz damping AC voltage, the damping AC voltage generated by the system during the test process can reach 60kV, and it is combined with advanced system hardware and system software for diagnosis.
The latest power electronic semiconductor technology
The latest laser control technology
Advanced digital signal processor and filtering technology
Advanced wireless network control technology.
2. The measurement and analysis software can perform remote data analysis under the condition of a network.
3. Full English operation interface, capable of recording oscillating voltage waveforms and partial discharge signal waveforms, and making real-time dots during the pressurization process;
4. Automatically display the frequency, amplitude and sampling time width of the oscillating voltage waveform.
5. It can automatically analyze the waveform expansion of the tested partial discharge signal.
6. Automatically display the dielectric loss test value.
7. Automatically generate a partial discharge location map and generate statistical reports, and automatically generate a partial discharge statistical map.
Specification
Output voltage |
Maximum: ±60kVpeak |
Oscillation frequency range |
20Hz~850Hz |
Inductance |
1.0H~2.1H (optional) |
Data analysis |
Manual analysis, automatic analysis (analog and digital filtering) |
Capacitance range to be measured |
0.05~5uF |
High voltage charging current |
10mA |
Partial discharge test range |
10pC~200nC |
Measurement accuracy |
±0.1pC (sampling 14bits) |
Wave speed |
50-300m/us |
Locating accuracy |
±0.1m |
Locating error |
≤1%×cable length |
PD level detection |
According to IEC60270 |
PD locating bandwidth |
100kHZ~50MHZ automatic or manual selection |
Dielectric loss value tan δ |
0.1%~10% |
Supply voltage |
180V~250V, AC 50Hz |
Operating temperature |
-120ºC~ + 60ºC |
Weight |
About 88kg |
Size |
Diameter 650mm, height 980mm |
Interface |