Customization: | Available |
---|---|
After-sales Service: | Yes |
Warranty: | 1 year |
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
General introduction
GDHG-106B is a multifunctional tool specially designed for analyzing current transformers and voltage transformers of protection or measurement use. The operator only needs to set values for test current and voltage, the instrument will automatically boost voltage and current, and then show test results in a short time. Test data can be saved, printed, and uploaded to PC through USB interface.
CT (protection type, metering type) | PT |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Item | Parameter | |
Power supply | AC220V±10%, 50Hz | |
Output | 0-2500Vrms, 5Arms (20A peak) | |
Output current | 0-1000A | |
Accuracy of excitation | ≤0.5%(0.2% of the reading+0.3% of the range) | |
Secondary winding resistance measurement | Range | 0.1-300Ω |
Accuracy | ≤1.0% (0.4% of the reading+0.6% of the range) | |
Secondary actual burden measurement | Range | 5-500VA |
Accuracy | ≤0.5% (0.2% of the reading+0.3% of the range) ±0.1VA | |
Angular error measurement | Accuracy | 4min |
Resolution | 0.1min | |
CT ratio measurement | Range | ≤25000A/5A (5000A/1A) |
Accuracy | ≤0.5% (0.2% of the reading+0.3% of the range) | |
PT ratio measurement | Range | ≤500KV |
Accuracy | ≤0.5% (0.2% of the reading+0.3% of the range) | |
Operation environment | Temperature: -10ºC-40ºC, Humidity: ≤90%, Altitude: ≤1000m | |
Dimension & Weight | Dimension: 345mm × 445mm × 380mm Weight: about 30kg |