• HVHIPOT GDSL-BX-200 Primary Current injection test system
  • HVHIPOT GDSL-BX-200 Primary Current injection test system
  • HVHIPOT GDSL-BX-200 Primary Current injection test system
  • HVHIPOT GDSL-BX-200 Primary Current injection test system
  • HVHIPOT GDSL-BX-200 Primary Current injection test system
  • HVHIPOT GDSL-BX-200 Primary Current injection test system

HVHIPOT GDSL-BX-200 Primary Current injection test system

Display: Digital
Installation: Portable Precise
Accuracy: 1
Power Source: AC and DC
Theory: Electric Apparatus
Application: Electronic Equipment, Electric Power
Customization:

360° Virtual Tour

Diamond Member Since 2011

Suppliers with verified business licenses

Manufacturer/Factory & Trading Company

Basic Info.

Model NO.
GDSL-BX-200
Display Ammeter Type
Single-phase Digital
Customized
Customized
Power Supply
AC 220V 50Hz.
Capacity
3kVA
Output Current
500A in Series, 1000A in Parallel
Output Voltage
6V in Series, 3V in Parallel
Accurancy
1%
Secondary Injection Current
50A
Test Range
0.001s-999.999s
Duty Cycle
5mins on, 10mins off
Transport Package
Wooden Case
Specification
ISO, SGS
Trademark
HV Hipot
Origin
China
HS Code
9030339000
Production Capacity
2000PCS/Year

Product Description

HVHIPOT GDSL-BX-200 Primary Current injection test system

GDSL-BX-200 Primary Current Injection Test Set, is mainly used in calibration for current transformer, motor protector, air switch, switch cabinet, circuit breaker, protection screen and etc.  


Features
  • Digital control, high anti reference ability.
  • Adapts autotransformer regulator which with low power consumption and large capacitance.
  • Converter has high permeability core .
  • Quick connects, lock design, have good current capability.
  • PVC panel.
  • Build-in quick plug with high safety.
  • Current range can be changed, easy to read.
  • Engineering plastics box, IP67 dustproof and waterproof.
  • Portable design is suitable for on site testing.
  • Zero start function to prevent the test objects from damage caused by high current impulsing. The equipment only can be started at zero.
  • Impulse choose function: The current value can be outputted directly without zero protection function when the equipment is under the testing for circuit breaker.
  • 0-50A AC current can be outputted, suitable for over current quick break testing of secondary protection.
  • Action time can be tested synchronously.
  • More calibrations can be series connected at same time to improve working efficiency .
  • To display the testing value of primary current, secondary current directly, convenient for CT/PT turn ratios calibration test. (Optional)

Specifications
Output current 0-1000A AC in parallel, 0-500A AC in series
Capacity 3kVA.
Output voltage 3V in parallel, 6V in series.
Input voltage AC220V, Single phase, 50Hz.
Current can be adjusted smoothly and continuously, accuracy level 1.0
Output current is standard sine wave, wave distortion is less than 5%.
Secondary injection current 50A
Output current RMS continuous adjustable.
The action time of test object can be tested, the lock action time is also can be recorded at same time.
Test range 0.001S~999.999S, resolution 1ms, error: 0.005% range: ±2digs
Capacity is designed as 5 minus for short and discontinuous working.
Duty Cycle 2.5mins ON, 10mins OFF if in batch test
 
  • HVHIPOT GDSL-BX-200 Primary Current injection test system
  • HVHIPOT GDSL-BX-200 Primary Current injection test system
     

Send your message to this supplier

*From:
*To:
*Message:

Enter between 20 to 4,000 characters.

This is not what you are looking for? Post a Sourcing Request Now