Customization: | Available |
---|---|
Task: | Partial Discharge Testing Machine |
Structure: | Combination |
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
GDJF-2006 Digital Partial Discharge Detector is widely used for detecting partial discharge of high voltage equipment such as power transformers, instrument transformer, HV circuit breaker, Zinc oxide surge arrester, power cable. It also can make type tests and monitor insulation operation.
Capacitance range | 6pF-250μF |
Sensitivity | <0.02pc (capacitance at 50pF) |
Amplifier | 3db low frequency fl 10kHz, 20kHz, 30kHz, 50kHz, 80kHz. 3db high frequency fh 100kHz, 200kHz, 300kHz, 400kHz, 500kHz. |
Gain adjustment range | >120db, gain difference 20±1db, asymmetry of positive/negative pulse response<1db |
Time window | Width 1°-360°, can be rotated at any time. |
Test voltage | 0-200kV, error <3% F.S. |
Acquisition channel | 4 or 6 channels/card. |
Input impedance | 1MΩ. |
Max. Sampling rate | 20Mhz. |
AD resolution | 12bit, DC accuracy 0.2%. |
Sampling length of each channel | 8M. |
Triggering mode | Manual, internal triggering, external triggering. |
Bandwidth of acquisition card | 3Mhz(-3db). |
Weight | About 15kg. |
Principle diagram