Customization: | Available |
---|---|
Hv Output: | 0.5-10kv |
Capacity: | 1500va |
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
Working condition | -15ºC~40ºC | RH<80% | |||||
Anti-interference principle | Frequency conversion | ||||||
Power supply | AC 220V±10% | Generator can be used. | |||||
High voltage output | 0.5KV~10KV | Every 0.1kV | |||||
Accuracy | 2% | ||||||
Max. current | 200mA | ||||||
Capacity | 2000VA | ||||||
Self-excitation power | AC 0V~50V/15A | 45HZ/55HZ 47.5HZ/52.5HZ 55HZ/65HZ 57.5HZ/62.5HZ Automatic dual frequency |
|||||
Resolution | tgδ: 0.001% | Cx: 0.001pF | |||||
Accuracy | tgδ: ±(reading*1.0%+0.040%) | ||||||
C x: ±(reading*1.0%+1.00PF) | |||||||
Measurement range | tgδ | Without limit | |||||
C x | 15pF < Cx < 300nF | ||||||
10KV | Cx < 60 nF | ||||||
5KV | Cx < 150 nF | ||||||
1KV | Cx < 300 nF | ||||||
CVT test | Cx < 300 nF | ||||||
LCR measurement range | L>20H(2kV) | R>10KΩ(2kV) | |||||
LCR measurement accuracy | 0.1% | Angle resolution | 0.01 | ||||
CVT ratio range | 10~10000 | ||||||
CVT ratio accuracy | 0.1% | ||||||
CVT ratio resolution | 0.01 | ||||||
Dimension | Main unit: 350(L)×270(W)×270(H) | ||||||
Accessory box: 350(L)×270(W)×160(H) | |||||||
Memory capacity | 200 groups, USB flash disk storage is supported. | ||||||
Weight | Main unit: 22.75Kg | ||||||
Accessory box: 5.25Kg |