HVHIPOT New GD-4132G Underground Cable Fault Locator
Cable fault locator GD-4132G, can work together with high -voltage signal generator, is a portable, intelligent power cable fault locator.
Background noise reduction function, effectively filter out environmental interference noise, highlight the discharge sound of the fault position.
Intelligent fixed -point method, directly give the sound magnetic delay value through the intelligent algorithm to reduce the requirements for testers.
Automatic dumb function, automatically mute when moving sensors, avoid the noise of moving the sensor and damage the ears.
Electronic compass function, display the left and right positions and angles of the cable laying direction with the sensor.
Sound channel filter parameters can be adjusted, select the appropriate filter parameter to suppress environmental noise.
Automatic gain function, magnetic field trigger gains automatic adjustment, more convenient for fixed points.
High -performance anti -noise monitoring headphones.
800 *480 high -bright colored LCD, the brightness reaches 800cd/m2, to ensure visual in the sun.
Built -in large -capacity lithium -ion battery power supply, USB interface charging.
Small and portable, light weight.
Specification
1. Sound magnet synchronization pin-pointing function:
(1) Sound channel
a) Band width
Full channel: 80Hz ~ 1500Hz.
Low channel: 80Hz ~ 400Hz.
High channel: 200Hz ~ 1500Hz.
Band channel: 150Hz ~ 600Hz.
b) Maximum signal gain:> = 80db.
c) Pin-pointing accuracy: 0.1m.
(2) Magnetic field channel
a) The maximum gain of the signal:> 80db
2. Sound -magnet synchronous background noise reduction mode
Support three modes: strong noise reduction, adaptive noise reduction, no noise
reduction.
3. Power:
a) Battery: Built -in lithium -ion battery group with a nominal voltage of 3.7V and a capacity
of 6700mAh.
b) Use time, continuous use time> 9 hours.
c) Charger: Enter AC100-240V, 50/60Hz; output 5V/2A.
d) Charging time: <5 hours.
4. Display method: 800*480 highlight color LCD, visible in the sun
5. Dimension: Host 230*127*55mm.
6. Weight: main unit 1kg; sensor 1.4kg
7. Use conditions: temperature: -10ºC -40ºC, humidity 5-90 % RH, altitude <4500m