Customization: | Available |
---|---|
After-sales Service: | Yes |
Warranty: | 1 year |
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
Use condition | -20ºC- 50ºC | RH<80% |
Charging power supply | AC 220V±10% | |
Input range of PT reference voltage | 0-300V | |
Input resistance of voltage channel | ≥150kΩ (with fuse) | |
Measuring accuracy of PT reference voltage | ± (2% of the reading+0.5V) | |
Measuring range of current input | 0-10mA | |
Measurement accuracy of current fundamental | ± (2% of the reading+5μA) | |
Measurement accuracy of current harmonic | ± (5% of the reading+10μA) | |
Input resistance of current channel | ≤1Ω | |
Measurement range of electric field strength | 30kV/m ~ 300kV/m | |
Accuracy of electric field strength | ±10% of the reading | |
Action times of monitor | 0-99times | |
8/20μS impulse current | ≥50Ap | |
Calibration range of current meter | 0-10mA | |
Calibration accuracy of current meter | ± (2% of the reading+5μA) | |
Measurement resolution |
Voltage | 0.001V |
Current | 0.001mA | |
Angle | 0.001° | |
Battery working time | Main unit 8hours, voltage sampling box 12hours | |
Wireless transmission distance | 1000meters and above (empty and unobstructed) | |
Dimension of main unit | 320×270×140mm | |
Handheld collection probe | 180×120×80mm | |
Weight of main unit | 4kg (without accessories) |