• 10kV 2kVA GDYD-BX-12 Digital AC Hipot Tester
  • 10kV 2kVA GDYD-BX-12 Digital AC Hipot Tester
  • 10kV 2kVA GDYD-BX-12 Digital AC Hipot Tester
  • 10kV 2kVA GDYD-BX-12 Digital AC Hipot Tester
  • 10kV 2kVA GDYD-BX-12 Digital AC Hipot Tester
  • 10kV 2kVA GDYD-BX-12 Digital AC Hipot Tester

10kV 2kVA GDYD-BX-12 Digital AC Hipot Tester

Type: Universal Testing Machine
Accuracy Grade: 3%
Load Way: Electronic Load
Loading Method: Dynamic Load
Display: Digital
Control: Computer Control
Customization:

360° Virtual Tour

Diamond Member Since 2011

Suppliers with verified business licenses

Manufacturer/Factory & Trading Company

Basic Info.

Model NO.
GDYD-BX-12
Weight
36kg
Power Source
AC220V
output voltage
AC 0-10kV
capacity
2kVA
current
AC 0-200mA
Transport Package
Standard Export Plywood Case
Specification
ISO9001
Trademark
HV HIPOT
Origin
Wuhan, China

Product Description

One Piece Design GDYD-BX-12 AC Hipot Test Set 10kV 2kVA


I. General information

AC hipot testing is the effective and direct way to test insulation strength for electrical equipment, apparatus or machines. It checks dangerous flaws which assure electrical equipment continuous working.
Typical applications include testing of transformers, switchgear, cables, capacitors, aerial motors platforms, hot sticks bucket bricks, vacuum bottles and other related equipment like vacuum interrupters, blankets, ropes, gloves, hydraulics hose, instruments transformers generators.


II. Features
 
  1. Monitoring function: HV voltage, HV current, LV current, zero position indicator, power indicator, work indicator, timing indicator
  2. Protection function: over current protection, zero start protection, sound and light alarm reminder
  3. New type time relay is adopted, and the timing range is wider (1S~99H)
  4. The use of a new type of current relay is more accurate and reliable to ensure the safety of people and equipment.
  5. The high-voltage coil of the test transformer is a cylindrical multi-layer tower type, wound by high-quality polyester enameled wire and high-voltage insulation material.
  6. Light weight, small size, convenient movement and superior performance.


III. Specifications
Input AC220V ± 10%
Frequency 50Hz/60Hz ± 1
 Output voltage AC 0-10kV
LV current 0-10A
Capacity 2kVA
HV current 0-200mA
Output control Manual control
Voltage accuracy 3% (F.S)± 1digital
Current Accuracy 3% (F.S)± 1digital
Timing  0-99H
Weight 26kg
Humidity 85% RH
Environmental temperature -20ºC~50ºC
Size 430*540*410 mm


IV. Working Principle


This device is composed of a contact voltage regulator, control circuits, protection circuits, measurement circuits and signal circuits. It is by connecting to the power frequency power supply and adjusting the voltage regulator (that is, the input voltage of the test transformer) to obtain the required test high voltage voltage value.