GDDJ-DGA Transformer Oil Gas Analyzer is an online monitoring device for dissolved gas in transformer oil based on gas chromatography technology. Potential fault are determined, release alert as per preset value through expert diagnosis system.
The device adopts distributed control sampling technology and has self-diagnosis and self-recovery functions. Each function module is weak coupling, function independent, adopting rack structure, easy for engineering maintenance.
Specifications
Environmental temperature |
-40ºC~+70ºC |
||
Environmental humidity |
Relative humidity 5-95%(no condensation) |
||
Atmospheric Pressure |
80kPa-110kPa |
||
Power supply |
AC 220V±10%, 50Hz |
||
Monitoring components |
H2, CO, CO2, CH4, C2H4, C2H2, C2H6, H2O, growth rate and concentration |
||
Analysis and diagnostic function |
Analyze and diagnose monitoring data by three-ratio method, David triangle method and cube diagram method. Original spectrogram can be supplied. |
||
Min. Detection cycle |
40-60mins, user-defined, default four times a day. |
||
Sampling mode |
Cycling sampling, to reflect real-time situation of inside gas. |
||
Separating mode of oil and gas |
Vacuum degassing mode, degassing for three times continuously. |
||
Data storage lifespan |
≥ 10 years |
||
Carrier gas quantity |
Self-made carrier gas, not interrupted all year round. No need to replace gas cylinder. |
||
Monitoring gas |
Measuring range |
Min. detection |
Error |
H2 |
2- 2000 ppm |
1 ppm |
±10% |
CO |
5- 20000 ppm |
5 ppm |
±10% |
CH4 |
0.2- 2000 ppm |
0.2 ppm |
±10% |
C2H4 |
0.2- 2000 ppm |
0.2 ppm |
±10% |
C2H6 |
0.2- 2000 ppm |
0.2 ppm |
±10% |
C2H2 |
0.2- 2000 ppm |
0.2 ppm |
±10% |
CO2 |
25- 20000 ppm |
25 ppm |
±10% |
H2O |
1 - 800 ppm |
||
Oil temperature |
-40ºC~200ºC |
||
Total air quantity |
0.2-15% |
||
Total hydrocarbon |
1 - 8000 ppm |
||
Stability (measurement error) |
At the same testing condition, error is no more than 10% for the same oil sample. (medium concentration) |
||
IP class |
IP66 |