| Customization: | Available |
|---|---|
| Brand: | HV Hipot |
| Customized: | Customized |
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
| Measuring principle | Non-dispersive infrared sensor (NDIR) |
| Measuring range | double path 0-2000ppmv (resolution 0.1) 0-50ppmv (resolution 0.01) limit range 0-100% |
| Resolution | 0.1ppmv and 0.01ppmv |
| Accuracy | ±2%FS |
| Repeatability error | ≤±1% |
| Response time | ≤10s |
| Recovery time | ≤15s |
| Long time stability(span) | ≤±20ppm, more than 1000 hours |
| Long time stability(zero) | ≤±20ppm, more than 1000 hours |
| Zero shift | ≤±1%(F.S/year) |
| Linear error | ≤±1% |
| Storage temperature | -20 ~ +60ºC |
| Operation temperature | -20 ~ +50ºC |
| Working humidity | 0-95% (no condensation) |
| Sampling mode | Diaphragm pump, flow up to 1L/min. |
| Working voltage | 220VAC±10%, 50Hz or Battery F750/8.4V. |
| Air pressure | 800-1150hPa |