I.General information
GDYD-100kVA-24kV AC Hipot Tester is composed of control unit, external regulator and oil testing transformer (HV unit) which output AC voltage smoothly. Meanwhile, it has many monitoring and protection functions.
II.Features
7-inch color LCD screen, with PLC automation control.
Voltage, LV voltage, LV current measured at the same time, with high precision sensor and high performance collection chip.
Automatic mode and manual mode for option.
Display HV voltage, LV voltage, LV current, time and withstanding result.
Over-voltage and over-current protection. Output voltage, HV current upper limit, LV current upper limit and timing can be set.
Zero-starting function. Test can be proceed after the voltage is back to zero.
Store up to 8000 pcs data in 3 months. It has USB port to upload data to USB disk.
When setting voltage is arrived, it will timing automatically. After timing, voltage will be back to zero.
When the LV current is over setting value, the voltage will be cut off automatically and it will be back to zero. When the HV current is over setting value, the test object will be cut off and test can be proceed continuously.
With anti-interference ability, suitable for electromagnetic environment.
With wheels for both control unit and HV unit, easy to move.
III. Specifications
Control unit specifications
Power: AC 380V±10%,50Hz
Capacity: 100kVA
Output: AC 0-400V
Rated output current: 250A
HV voltmeter range: 0-24kV
Accuracy: 1.5% of the reading±1digit(F.S)
HV ammeter range: 0-4167mA
Accuracy: 1.5% of the reading±1 digit(F.S)
LV ammeter range: 0-250A
Accuracy: 2.0% of the reading±1 digit(F.S)
Timing range:1s-99h
Weight: about53kg
Dimension: 535mm (L)*575mm (W)*1070mm (H)
B. Regulator specifications
Capacity: 100kVA
Input voltage: 0-380V
Output voltage: 0-430V
Rated current: 250A
Weight: about 398kg
Dimension: 900*650*1590mm
C. Testing transformer (HV unit) specifications
LV side voltage: 0-400V
LV side current: AC 0-250A
HV side voltage: AC 0-24kV
HV side current: AC 0-4.15A
Capacity: 100kVA
HV side/LV side turns ratio:60:1
Measuring voltage: AC 0-250V
Accuracy: 1.5% of the reading±1 digit(F.S)
No-load current: less than 4%
Impedance voltage: less than 12%
Weight: about 260kg
Dimension: 580mm(L)*380mm(W)*850mm(H)
Working conditions
Working place: No gas, steam, chemical dust and explosive and corrosive medium which will influence insulation.