| Customization: | Available |
|---|---|
| Type: | Universal Testing Machine |
| Accuracy Grade: | 0.1 |
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
| Accuracy level | 0.1 class |
| Output voltage | 3*100V/57.7V Y 3*100V 3*380V/220V Y 3*380V Regulating range: 0-120% continuously adjustable Regulating fineness: better than 0.01% * Special voltage range can be set up according to user order. |
| Current range | 0.1A, 0.25A, 0.5A, 1A, 2.5A, 5A, 10A, 20A, 50A, 100A Regulating range: 0-120% consecutively adjustable Regulating fineness: better than 0.01% |
| Output power | (voltage loop) 800VA (current loop) 1200VA |
| Stability of output voltage, current and power | ≤0.05%/120S PF=1 (0.1 class type) |
| Wave distortion of output voltage and current | ≤0.5% |
| Symmetry of three phase | better than 120° +0.3° |
| Frequency range | 45Hz~65Hz |
| regulating accuracy | 0.1 Hz |
| Phase shifting range | -180.0°-180.0° |
| Regulating accuracy | 0.1° |
| Standard crystal oscillator stability | ≤10-7/s |
| Indicating instruments class | Voltmeter and ammeter accuracy: level±0.2% Phase meter accuracy: ±0.5° Frequency meter accuracy: ±0.01Hz |
| Maximum meters for test | 20 |
| Power supply | 3*220V±10%, 50Hz |
| Maximum power consumption | 3200VA |
| Working temperature | 20±5ºC |
| relative humidity | ≤85% |
| Dimensions | 2500mm * 750 mm * 2000 mm |
| Weight | 400kg |