GDYD-770A AC/DC Hipot Test Set is composed of automatic control unit and oil testing transformer(HV unit) which output ACvoltage smoothly. Meanwhile, it has many monitoring and protection functions.
II.Features
10inch color LCD screen, with PLC automation control.
HV Voltage, HV current, LV voltage, LV current measured at the same time, with high precision sensor and high-performance collection chip.
The human-machine interface adopts full touch and partial key operation mode, intelligent working process, optional automatic mode, and manual mode.
Display HV voltage, HV current, LV voltage, LV current, time, and withstanding result.
Over-voltage, over-currentand flashover protection. Output voltage, HV protection current, LV protection current (hardware has been set), mA meter protection current and timing time can be set.
Support stage boosting (5 stages), and the voltage value of each stage can be arbitrarily set to facilitate the detection of test object problems.
Zero-starting function. Test can be proceeded after the voltage is back to zero.
Store up to 8000pcs data in 3months.
When setting voltage is arrived, it will be timing automatically. After timing, voltage will be back to zero.
When the LV current is over setting value, the voltage will be cut off automatically and it will be back to zero. When the HV current is over setting value, the test object will be cut off and test can be proceeded continuously.
With anti-interference ability, suitable for electromagnetic environment.
Automatic error diagnosis, easy to find and solve problems, simple and convenient maintenance of equipment.
III. Specifications
Control unit specifications
Input voltage: AC433V±10%, 50Hz±1%
Output capacity: 70kVA.
Low voltage output: AC 0~400V
Output current: 175A (Max)
Low voltage measurement range: 0-400V resolution: 0.1V
Low-voltage current measurement range: 0.2-175A, resolution: 0.1A
High voltage measurement range: AC0-70kV, resolution: 0.01KV
High voltage current measurement range: AC1.0-1000mA, resolution: 0.01mA
Timing range: 0-999s
Voltage accuracy ≤±3.0%FS
Current accuracy ≤±3.0%FS
Testing transformer (HV unit) specifications
Output capacity: 70kVA.
Low voltage (input) voltage: AC 0~400V
Low voltage (input) current: AC 0-175A
High voltage (output) voltage: AC0-70kV
High voltage (output) current: AC 0-1000mA
Measurement ratio: 700:1 Error: ±1%
Impedance voltage: ≤12%.
No-load current: ≤10%.
Running time: 5min ON at rated capacity, 5min OFF continuous cycle duty system, long-term operation at 1/3 rated voltage and 1/3 rated current.
C. Working conditions.
Power supply voltage: 433V±10%, 50HZ±1%, the waveform distortion rate is not more than 5%.
Ambient temperature: -5ºC-40ºC
Ambient humidity: ≤80%RH, no condensation, no flickering of the instrument
Altitude: ≤1000m
The working environment should be free from obvious dust, smoke, corrosive, flammable gas, water vapor and salt spray, and no serious vibration.