HVHIPOT GDTF-4500/750 Variable Frequency AC Resonant Test System for GIS

Product Details
Customization: Available
After-sales Service: yes
Warranty: 1 year
Manufacturer/Factory & Trading Company

360° Virtual Tour

Diamond Member Since 2011

Suppliers with verified business licenses

Audited Supplier

Audited by an independent third-party inspection agency

Management System Certification
ISO9001:2015, ISO14001:2015, ISO 45001:2018
Export Year
2011-07-01
  • HVHIPOT GDTF-4500/750 Variable Frequency AC Resonant Test System for GIS
  • HVHIPOT GDTF-4500/750 Variable Frequency AC Resonant Test System for GIS
Find Similar Products

Basic Info.

Model NO.
GDTF-4500/750
Type
Universal Testing Machine
Accuracy Grade
1.5
Load Way
Electronic Load
Loading Method
Dynamic Load
Display
Digital
Control
Computer Control
Weight
0-100Kg
Power Source
AC380V
Rated capacity
4500kVA customized
Rated voltage
500, 750kV
Rated current
9A, 6A
Working Frequency
30-300Hz
Output waveform
sine wave
Transport Package
Standard Export Wooden Box
Specification
ISO, SGS
Trademark
HV Hipot
Origin
Wuhan, China
HS Code
9030899090
Production Capacity
300set/Year

Product Description

GDTF-4500/750 Variable Frequency AC Resonant Test System

Test Object and Requirement

The system is specially designed for AC withstand voltage test for below items, with below specifications and requirements.
Test Object Specifications Test Frequency Test Voltage Test Time
GIS, CT/PT, switch 400kV 30-300Hz 750kV 1min
GIS, CT/PT, switch 245kV 30-300Hz 500kV 1min

Working Environment
  • Environmental temperature: -10ºC to 50ºC
  • Related humidity: ≤ 90% RH
  • Altitude: ≤ 3km
 
Technical Data
  • Rated capacity: 4500kVA
  • Input power supply: Three phase 380V, 50Hz
  • Rated voltage: 500, 750kV
  • Rated current: 9A, 6A
  • Working Frequency: 30-300Hz
  • Output waveform: sine wave
  • Waveform distortion rate: ≤1%
  • Working time: constant working of 5mins under rated load. Working of 1min, under 1.1 times of rated voltage
  • Temperature rise: ≤65K after constant working of 5mins under rated load
  • Quality factor: Q ≥30 (f=45Hz)
  • Protective function: Over-current, over-voltage and flash-over protections for test object.
  • Accuracy: 1.5% (RMS)

HVHIPOT GDTF-4500/750 Variable Frequency AC Resonant Test System for GIS
HVHIPOT GDTF-4500/750 Variable Frequency AC Resonant Test System for GIS
HVHIPOT GDTF-4500/750 Variable Frequency AC Resonant Test System for GIS

 

Send your message to this supplier

*From:
*To:
*Message:

Enter between 20 to 4,000 characters.

This is not what you are looking for? Post a Sourcing Request Now
Contact Supplier