Customization: | Available |
---|---|
Display: | Digital |
Installation: | Direct Connected |
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
No. | Items | Description |
1 | Voltage/Current/Frequency | Measure three phase voltage, zero line voltage, three phase current, zero line current, frequency. |
2 | Harmonic wave measure | Measure up to 50times harmonic wave, results include each time harmonic wave voltage, current amplitude, total distortion rate of voltage harmonic wave, every times voltage harmonic ratio/current harmonic ratio, harmonic frequency spectrogram display. |
3 | Power measure | Measure three phase apparent power, active power, reactive power, power factor, three phase electric energy. |
4 | Three phase unbalance measure | Measure three phase voltage unbalance, positive sequence, negative sequence, zero sequence voltage; three phase current unbalance and positive sequence, negative sequence, zero sequence current; voltage vector and current vector display. |
5 |
Monitoring record | Long time record basic(steady state) electric energy parameters, record time is 3s to 30mins adjustable. |
6 | Digital oscilloscope | Check voltage/current signal wave form |
Measure range | Measure accuracy | Remark | |
Voltage/current /frequency |
Three phase voltage : 10-700V(effective value) Zero line voltage: 1-700V(effective value) Three phase current : 0-1000A(effective value,1000A current sensor for optional) Zero line current : 0-25A (effective value, 25A current sensor for optional) Frequency: 40-70Hz |
Voltage: ±0.5% Current: ±0.5% Frequency: reading±0.01Hz |
Here,we use A phase voltage frequency as measured frequency |
Harmonic wave measure |
Voltage harmonic: total harmonic 1-50times harmonic wave. Current harmonic: total harmonic 1-50times harmonic wave. |
Voltage harmonic wave: ±0.1(%f) Current harmonic wave: ±1% |
|
Power measure | Active power: 0.05-700kW Apparent power: 0.05-700kVA Reactive power: 0.05-700kVAR Power factor: 0.00-1.00 Active power energy: 0.01-10000kWh Apparent power energy: 0.01-10000kVAh Reactive power energy: 0.01-10000kVARh Average power factor: 0.00-1.00 |
Active: ±2% Apparent: ±2% Reactive: ±2% Power factor: reading±0.005 Active power energy: ±2% Apparent power energy: ±2% Reactive power energy: ±2% Average power factor: reading±0.005 |
|
Three phase unbalance |
Fundamental voltage: 10-700V(effective value) Fundamental current: 0.5-1000A(effective value) Fundamental frequency: 40-70Hz Phase angle: 0-360degree Unbalance: 0.0%-100% |
Voltage: 0.5% Current: 0.5% Frequency: reading±0.01Hz Phase angle: reading±0.3degree Voltage unbalance: reading±0.2% Current unbalance: reading±0.2% |
Here,we use A phase voltage frequency as total measurement frequency |
Monitoring record | Record parameters include three phase voltage, three phase current, zero line current, voltage harmonic wave(total harmonic, 1-25 times harmonic), current harmonic wave(total harmonic, 1-25 times harmonic), three phase unbalance, active power, power factor, fluctuation, flicker |
Recording time=(max. Recording numbers*storage time i nterval)/60mins Max. Recording numbers: 18635pcs Storage time interval: 3s-30mins Recording time: 15hours-388days |
If storage time interval is set as 3s, 15.5hours can be monitored; if storage time interval is set as 30mins, 388days can be monitored. 3s-30mins is adjustable. |
Dips and swells | Voltage dips and swells and temporary outage | Record up to 40pcs events | |
Fluctuation | Voltage fluctuation quantity: 0.1%-10.0% | Measure error: ≤±5% | |
Flicker | Short time flicker, long time flicker | Short time flicker measurement error: ±5% Long time flicker measurement error: ±5% |
|
Digital oscilloscope | Three phase voltage, three phase current, zero line voltage and zero line current instant wave form |
Max.sampling frequency: 200kHz Min.sampling frequency: 100Hz |
|
Dimension | 278*152*85mm | Weight | 1.6kg |