Customization: | Available |
---|---|
Power supply: | AC 220V±10% |
Measuring output current: | 1A~50A adjustable |
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
GDWR-30A Earth Resistance Tester is a high-precision test instrument used in various fields such as substations for testing Soil Resistivity, Ground Grid Impedance, Earth Surface Potential and Step Voltage and related parameters. The instrument has the characteristics of small volume, light weight, convenient carrying, strong anti-interference performance and high accuracy. The instrument is an integrated structure, built-in variable frequency power supply module, and the output power supply is continuously variable frequency adjustable. The frequency can be changed to 45Hz or 55Hz, and the built-in high-speed processor core adopts high-end digital filtering technology, which effectively avoids the interference of the power frequency electric field to the test, and fundamentally solves the problem of accurate measurement under strong electric field interference. A large number of on-site tests and user usage indicate that when the grounding grid is tested under the harsh electromagnetic environment of the running substation, the measured data of the grounding impedance tester of the special frequency ground grid are accurate and repeatable. It is an ideal instrument for the measurement of the characteristic parameters of large and medium grounding grids.
1 | Use condition | -15ºC~40ºC | RH<80% |
2 | Anti-interference principle | Frequency conversion method | |
3 | power supply | Auxiliary power supply: AC220V±10% Main power supply: three-phase AC380V/Single phase 220V The output power is halved for single-phase power supply. |
Generator is allowable |
4 | Measure output current | 1A~50A adjustable | |
5 | Measure output voltage | 0V~800V | |
6 | Measuring frequency of power supply | 45, 50, 55, 60, 65Hz single frequency 45/55, 55/65 47.5/52.5Hz automatic dual frequency |
|
7 | Rated output power | 12kW | |
8 | Resolution |
Ground impedance: 0.0001Ω | |
Impedance angle: 0.0001° | |||
9 | Accuracy | Ground impedance: ±(1%*reading+0.002) | |
Impedance angle: ±(1%*reading+0.02°) | |||
10 | Resistance measurement range | 0.001Ω~5KΩ | |
11 | Dimensions | Host: 450 (L) × 350 (W) × 480 (H) Transformer: 450 (L) × 350 (W) × 540 (H) |
|
12 | Memory size | 100 groups, support U disk data storage |
|
13 | weight | Host: 20kg; Transformer: 55kg; Cables: 3kg; Ground pile: 4kg |