| CT (protection, measurement) | PT |
| Voltage current characteristic curve (excitation characteristic) | Voltage current characteristic curve (excitation characteristic) |
| Auto calculate knee point value | Auto calculate knee point value |
| Auto display 5% and 10% error curves | Turns ratio measurement |
| Turns ratio measurement (6 channels simultaneously) | Polarity determination |
| Differential measurement | Differential measurement |
| Phase measurement (angular difference) | Phase measurement (angular difference) |
| Polarity judgment | AC withstand voltage test |
| Primary current injection test | Second burden measurement |
| AC withstand voltage test | Secondary winding resistance test |
| Secondary burden test | |
| Secondary winding resistance test | |
| Comprehensive CT test (one-time wiring test for voltage current turns ratio) |
| Item | Parameter | |
| Power supply | AC220V±10%, 50Hz | |
| Output | 0-3000Vrms, 2Arms(20A peak) | |
| Output current | 0-1000A | |
| Accuracy of excitation | ≤0.5%(0.2%*the reading+0.3%*range) | |
| Secondary winding resistance measurement | Range | 0.1~300Ω |
| Accuracy | ≤1.0%(0.4%*the reading+0.6%*range) | |
| Secondary actual burden measurement | Range | 5-500VA |
| Accuracy | ≤0.5%(0.2%*the reading+0.3%*range) ±0.1VA | |
| Accuracy of angular error | Accuracy | 4min |
| Resolution | 0.1min | |
| Accuracy of ratio error | 0.05% | |
| CT ratio measurement | Range | ≤25000A/5A (5000A/1A) |
| Accuracy | ≤0.5% | |
| PT ratio measurement | Range | ≤500KV |
| Accuracy | ≤0.5% | |
| Operation environment | Temperature: -10ºC-40ºC, Humidity: ≤90%, Altitude: ≤1000m | |
| Dimension &Weight | Dimension: 410mm × 260mm × 340mm Weight: ≤22Kg |
|