| Customization: | Available |
|---|---|
| Rated Capacity: | 10kVA |
| Output Voltage: | 100kv |
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
| Name | Function |
| Hipot Test Control Table GDYD-10/100 | Controlling and voltage boosting for test object which boosted to the rated voltage. |
| PD-free Gas type transformer YDQW-10/100 | |
| Coupling capacitor TAWF-600pF/100kV | Transmitting partial discharge signal to partial discharge detector. |
| Protective resistor GR100kV | |
| Isolation filter LBQ-10kVA | Device of anti-interference caused by power supply. |
| Partial discharge detector GDJF-2008 | Detecting and displaying partial discharge capacity. |
| Other accessories |
| Power supply | 220V±22V,50HZ |
| Rated Capacity | 10kVA |
| Output Voltage: | 100kV, current: 100mA |
| Input Voltage: | 200V, current: 50A |
| short-circuit impedance: | ≤ 8% |
| Operation time | 60mins@100% rated voltage and current. Continuous working@ 50% rated voltage and current. |
| Wave form distortion rate:<5% when voltage regulator input voltage distortion rate <3%, within 10-100% rated voltage range. | |
| PD value | ≤8pC @ 100% rated voltage ≤5pC @ 80% rated voltage |