Basic Info.

Model NO.
GD-2138L
Certification
ISO9001
Customized
Customized
Color
Gray
Power supply
AC 220V; 50Hz and Built-in Chargeable battery
Fault distance
Max. 32km
Resolution
1m
Fade zone
1m
Impulse voltage
0-16kV
Rated energy
1024J
Ambient temperature
0-40ºC
Ambient humidity
<80% RH
Delivery time
Shipped in 40 days after payment
Transport Package
Wooden Case
Specification
ISO, SGS
Trademark
HV Hipot
Origin
Wuhan China
HS Code
9030899090
Production Capacity
1000 Sets/Year

Product Description

Product Description

GD2138 system includes:
1. GD-2138 Mainfraime.
2. GD-2132R Receiver, for trace and locating.
3. Accessories, including RF inductive Tracking Rod, Potential Difference Locating Rack with 2 pins, AF Stethoscope and Headphone (for Listening mode), Grounding Pin.


GD-2138 Features&Specifications

GD-2138 is the main body of cable fault locator, it can measure the distance of cable fault, trace the test cable, and locate the fault point.It detects high impedance flashover, high impedance leaking, high/low impedance earthing, short circuit, open circuit, poor contact.


Features
  • High Measuring Accuracy, 1m Resolution.
  • Large LCD and with Menu and function buttons, easy to operate.
  • Directly detect high impedance cable fault without burning.
  • Display the direct or relative distance between testing and fault points.
  • Auto search along the wave for inflexion, easy to measure fault distance.
  • Waveform Comparison Method helps to detect puzzling fault.
  • Wave velocity of test cable can be calibrated.
  • Test data and wave can be saved, viewed and printed.
  • Igniting sphere gap is inside the mainframe.

Specifications
Power supply AC220V and Built-in Chargeable Battery
Fault Distance Max. 32km
Resulution 1m
Fade zone 1m
Impulse voltage 0-16kV (0-32kV for option)
Rated energy 1024J (2048J at 32kV)
Ambient temperature 0-40ºC
Ambient humidity <80% RH
Dimension  750×570×1200mm
Weight 128kg
 

GD2132R Features&Specifications

GD-2132R receives the signals from RF Inductive Tracking Rod and Potential Difference Locating Rack, and AF Stethoscope. It is used to trace cable and locate cable fault. It uses RF electromagnetic induction method to probe the cable track and deepness, uses potential difference method or AF stethoscopy method to locate the fault point. It is applicable to the cables with metal.

Features

  • High Receive Sensitivity
  • Low Static Drift
  • High Accuracy and Reliability
  • Great Anti-interference's ability
  • LCD screen
  • AC/DC Power Source

Specifications

Max. Distance to trace and locate 20km, or 3km if Φ< 0.5
Impedance Range of fault point to locate 0-50MΩ
Locating Accuracy <±10cm
Probe Deepness <3m

Send your message to this supplier