Measurement channel | 2-4pcs independent measurement channel |
Sampling rate | Max. 100MHz of each channel |
Sensitivity | 1pc |
Measurement range | 1pc-10000pc |
Dynamic range | >80dB |
Bandwidth 3dB of measurement frequency band | 10kHz-30MHz |
Digital filter | Any setting within 50kHz-30MHz |
Power Supply | AC 220V±10%, 50Hz, power <50W |
Environment temperature | -20ºC-60ºC |
Relative humidity | ≤ 95% |
Altitude: | ≤3000m |
Measurement mode | Non-contact |
Signal transmission mode | Optical fiber |
Measurement signals: | Ultrasonic signal, electric signal |
Detecting frequency band | 50kHz~20MHz |
Signal transmission mode | 50Ω Coaxial Cable |
Sensitivity | 1pC |
Main unit | 1pc |
HFCT sensor | 1pc |
Acoustic electric integrated sensor | 1pc |
Square-wave generator | 1pc |
Coaxial cable 10M | 1pc |
Twin-core optical fiber | 1pc |
Ground cable | 1pc |
User's guide | 1pc |
Factory test report | 1pc |
b. Calibration
The square-wave generator special line passes through the high frequency current transformer, and then the high frequency current transformer BNC interface is connected with the BNC interface of the host machine marked with an electric signal.
(For example, adjust the square wave generator to 100pC step, then display 100pC in the software interface, namely the signal calibration. Specific use method is mentioned in software instruction)
c. HFCT is an open type design, the current transformer is installed on the ground wire of the cable joint, fastening.
(Note: closed gently when fastening. Fasten mode of current transformer adopts magnetic adsorption, may occur at the openings of damage to the transformer due to impact)
2. Acoustic electric detection (Adopts acoustic electric integrated sensor)
a. Using optical fiber to connect optical signal terminal of acoustic electric integrated sensor with optical signal terminal of the host, open the snap switch, switch step to optical signal terminal.
(Note: when using optical signals, host needs to power on, press the rocker switch on the right crone of host panel, when the switch indicator light is on, indicates the battery switch is turned on, can start testing.)
b. Put the acoustic electric integrated sensor near the discharge point, using high voltage insulation rod and optical fiber to isolate high voltage, detection under the case of no connection to the cable, the specific detection principle is shown as below: