| Customization: | Available |
|---|---|
| After-sales Service: | Yes |
| Warranty: | 1 year |
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
| CT (protection type, measurement type) | PT |
| Voltage current characteristic curve (excitation characteristic) | Voltage current characteristic curve (excitation characteristic) |
| Auto calculate knee point value | Auto calculate knee point value |
| Auto display 5% and 10% error curve | Turns ratio measurement |
| Turns ratio measurement | Polarity determination |
| Ratio error measurement | Ratio error measurement |
| Phase measurement (angular difference) | Phase measurement (angular difference) |
| Polarity determination | AC withstand test |
| Primary current injection test | Secondary winding resistance measurement |
| AC withstand test | Secondary burden measurement |
| Secondary winding resistance measurement | Demagnetization of iron core |
| Secondary burden measurement | |
| Demagnetization of iron core |
| Item | Parameter | |
| Power supply | AC220V±10%, 50Hz | |
| Output | 0-2500Vrms, 5Arms(20A peak) | |
| Output current | 0-1000A | |
| Accuracy of excitation | ≤0.5%(0.2%*the reading+0.3%*range) | |
| Secondary winding resistance measurement | Range | 0~300Ω |
| Accuracy | ≤0.5%(0.2%*the reading+0.3%*range) | |
| Secondary actual burden measurement | Range | 0-1000VA |
| Accuracy | ≤0.5%(0.2%*the reading+0.3%*range) ±0.1VA | |
| Accuracy of angular error | 4min | |
| Accuracy of ratio error | 0.05% | |
| CT ratio measurement | Range | 25000A/5A (5000A/1A)≥5A/5A |
| Accuracy | ≤0.5% | |
| PT ratio measurement | Range | ≤500KV |
| Accuracy | ≤0.5% | |
| Operation environment | Temperature: -10-40 degree, Humidity: ≤90%, Altitude: ≤1000m | |
| Dimension&Weight | Dimension: 440mm × 340mm × 380mm Weight: ≤35Kg |
|