| Customization: | Available |
|---|---|
| Display Type: | Digital Only |
| Certification: | ISO |
Suppliers with verified business licenses
Audited by an independent third-party inspection agency



| Test Voltage | 250V,500V,1.0kV,2.5kV,5.0kV | ||||||
| Test Voltage accuracy | ±5% | ||||||
| Resistance Range | Max. | 500GΩ~10TΩ | |||||
| Min. | 0.1MΩ | ||||||
| Accuracy Grade | 5.0 | ||||||
| High Voltage Display Error | ±( 5%•Ux + 1d ) | ||||||
| Leakage current range and error | 0.1nA~9.9mA 5% | ||||||
| Display range and error of absorption capacitance | 0.1pF~99μF 5% | ||||||
| Temperature measurement error | ±0.5ºC | ||||||
| Measurement error of air humidity | ±2%RH | ||||||
| Short circuit current | About 6mA | ||||||
| Voltage ripple | <3% | ||||||
| Insulation resistance | > 500 MΩ | ||||||
| Pressure | AC10.0kV 50Hz 1min | ||||||
| Power Supply | 12V Li-battery | ||||||
| Use time of full charge | 30 days 10times DAR & 5times PI daily test | ||||||
| Operating temperature and humidity | 0ºC ~ + 40ºC < 85%RH | ||||||
| Storage temperature and humidity | - 20ºC ~ + 50ºC < 90%RH | ||||||
| Size(mm) | 325(L)×250(W)×130(H) | ||||||
| Weight | about 3.7kg | ||||||
| measurement resistance error | |||||||
| Voltage | 250 V | 500 V | 1.0 kV | 2.5 kV | 5.0 kV | ||
| ±( 3%·Rx + 1d ) | 1GΩ | 2GΩ | 4GΩ | 10GΩ | 20GΩ | ||
| ±( 5%·Rx + 1d ) | 10GΩ | 20GΩ | 40GΩ | 0.1TΩ | 0.2TΩ | ||
| ±( 10%·Rx + 2d ) | 100GΩ | 200GΩ | 0.4TΩ | 1TΩ | 2 TΩ | ||
| ±( 25%·Rx + 2d ) | 500GΩ | 1TΩ | 2TΩ | 5TΩ | 10TΩ | ||