General Information
GDSF-311WPD is ideal instrument when it is necessary to test water content, purity and decomposition products of SF6 gas. The core component of dew point test is DRYCAP series sensors produced by Finland Vaisala company. With professional hardware chips and excellent software algorithms of STMicroelectronics, we have produced a new generation of gas moisture test instrument.
Application
Technical parameters
SF6 Humidity:
Measuring range | Dew point -100 ~ +30 ºC(support ppmv, etc. ). |
Dew point accuracy | +-0.5degree (when the dew point temperature is below 0 degree, the sensor output for the frost point). |
Repeatability | +-0.5 degree. |
Gas flow | SF6 adjustment in 0.5 ~ 0.9L/min; |
Measuring range | 0 ~ 100% SF6 |
Accuracy and repeatability | +-0.5%, nothing to do with the flow |
SF6 decomposition products
SF6 Humidity |
|
Measurement method |
Resistive and Capacitive measurement principle |
Ambient temperature |
-20ºC--+60ºC |
Measurement range |
dew point -80ºC--+20ºC(support ppmv) (when the dew point temperature is below 0 ºC, the sensor output is the frost point) |
Accuracy |
±1ºC |
Response time |
63% [90%] +20→-20ºC Td 5s[45s] -20→-60ºC Td 10s[240s] |
Resolution |
0.01ºC |
Repeatability |
± 0.5 ºC |
Display unit |
ºC, ppm, ºCP20(converted value at 20ºC) |
Gas flow |
400-600ml/min |
Flow display |
0-1000mL digital flow meter |
Sample gas pressure |
≤1MPa |
SF6 Purity |
|
Measurement method |
Infrared measurement principle (European sensor company NDIR series sensor) |
Ambient temperature |
-20ºC--+60ºC |
Measuring range |
0 ~ 100% SF6. |
Response time |
[90%] 60s |
Measurement error |
±0.5%FS |
Repeatability error |
±0.5% |
Resolution |
0.01% |
Display unit |
% |
SF6 Decomposition Products |
|
Measuring method |
Principle of electrochemical measurement (Swiss Mombas wave electrochemical series sensor) |
Ambient temperature |
-20ºC--+60ºC |
Measurement range |
SO2: 0~200PPmv H2S: 0~200PPmv CO : 0~500PPmv HF : 0~50PPmv |
Measurement error |
SO2 <10PPmv : ±0.3PPmv >10PPmv : ±3% H2S <10PPmv : ±0.3PPmv >10PPmv : ±3% CO <50PPmv : ±2PPmv >50PPmv : ±4% HF <10PPmv : ±0.3PPmv >10PPmv : ±3% |
Repeatability error |
SO2 <10PPmv : ±0.2PPmv >10PPmv : ±2% H2S <10PPmv : ±0.2PPmv >10PPmv : ±2% CO <50PPmv : ±2PPmv >50PPmv : ±2% HF <10PPmv : ±0.2PPmv >10PPmv : ±2% |
Resolution |
0.01PPmv |
Display unit |
PPmv |
Other Features |
|
Power supply |
220VAC±10%, 50Hz, AC/DC use, over-charge protection, continuous working is no lower than 8hours. |
Ambient temperature |
-20--+60ºC |
Environment humidity |
90%RH |
Gas flow |
400 ~ 600ml / min |
Flow rate display |
0~1000mL imported digital flowmeter |
Sample gas pressure |
≤1MPa |
Measurement value influence |
No effect of pressure and flow |
Dimension |
395*295*155mm |
Weight |
about 2kg |