Customization: | Available |
---|---|
After-sales Service: | Yes |
Warranty: | 1 year |
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
Rated test voltage gear | GD3126A(5KV) | GD3126B(10KV) | |||||||
250 V,500V,1.0kV,2.5kV,5.0kV | 250 V,500V,1.0kV,2.5kV,5.0kV,10.0kV | ||||||||
Output voltage error | ±5% | ||||||||
Measuring resistance range | Upper limit | 100GΩ~10TΩ | 100GΩ~20TΩ | ||||||
Lower limit | 0.1MΩ | 0.1MΩ | |||||||
Accuracy grade | 5.0 level | ||||||||
HV display error | ±( 5%•Ux + 1d ) | ||||||||
Temperature measurement error | ±0.5ºC | ||||||||
Measurement error of air humidity | ±2%RH | ||||||||
Short circuit current | About 6mA | ||||||||
Voltage ripple | <3% | ||||||||
Insulation resistance | > 500 MΩ (between test line and housing) |
||||||||
Withstand voltage | AC10.0kV 50Hz 1min(9/5000 (between test line and housing) |
||||||||
Power supply | 14.8V lithium battery | ||||||||
A full time charge using time | 30days 10times DAR& 5times PI daily test | ||||||||
Operating temperature and humidity | 0ºC ~ + 40ºC < 85%RH | ||||||||
Storage temperature and humidity | - 20ºC ~ + 50ºC < 90%RH | ||||||||
Size(mm) | 325(L)×250(W)×130(H) | ||||||||
Weight | about 3.7kg | ||||||||
Measurement resistance error | |||||||||
Voltage | 250 V | 500 V | 1.0 kV | 2.5 kV | 5.0 kV | 10.0 kV | |||
±( 3%·Rx + 1d ) | 1GΩ | 2GΩ | 4GΩ | 10GΩ | 20GΩ | 40GΩ | |||
±( 5%·Rx + 1d ) | 10GΩ | 20GΩ | 40GΩ | 0.1TΩ | 0.2TΩ | 0.4TΩ | |||
±( 10%·Rx + 2d ) | 100GΩ | 200GΩ | 0.4TΩ | 1TΩ | 2 TΩ | 4TΩ | |||
±( 20%·Rx + 2d ) | 500GΩ | 1TΩ | 2TΩ | 5TΩ | 10TΩ | 20TΩ |