Customization: | Available |
---|---|
After-sales Service: | 1 year |
Warranty: | 1 year |
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
GDHG-306D is CT/PT comprehensive tester, used for automatic testing of protection and metering CT/PT, which is suitable for laboratory and on-site testing. Reference standards IEC60044-2, IEC6044-1.
III. Specifications
Function parametersCT (protection type, metering type) | PT |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Item | Parameter | |
Power supply | AC220V±10%, 50Hz | |
Output | 0-3000Vrms, 2Arms(20A peak) | |
Output current | 0-1000A | |
Accuracy of excitation | ≤0.5%(0.2%*the reading+0.3%*range) | |
Secondary winding resistance measurement | Range | 0.1~300Ω |
Accuracy | ≤1.0%(0.4%*the reading+0.6%*range) | |
Secondary actual burden measurement | Range | 5-500VA |
Accuracy | ≤0.5%(0.2%*the reading+0.3%*range) ±0.1VA | |
Accuracy of angular error | Accuracy | 4min |
Resolution | 0.1min | |
Accuracy of ratio error | 0.05% | |
CT ratio measurement | Range | ≤25000A/5A (5000A/1A) |
Accuracy | ≤0.5% | |
PT ratio measurement | Range | ≤500KV |
Accuracy | ≤0.5% | |
Operation environment | Temperature: -10ºC-40ºC, Humidity: ≤90%, Altitude: ≤1000m | |
Dimension &Weight | Dimension: 410mm × 260mm × 340mm Weight: ≤22Kg |