GDYD-85D 5kVA/80kVAC, 110kVDC AC DC Hipot Test Set with dry type testing transformer

I. General information
GDYD series AC/DC Hipot Test Set is composed of manual control unit and AC/DC oil testing transformer(HV unit) which output AC or DC voltage smoothly. Meanwhile, it has many monitoring and protection functions.
II. Features
- Digital display meters mounted on the panel.
- Monitoring HV side voltage, HV side current, LV side current and indicator of zero, power, working start, timing.
- Over-current protection, zero-starting protection, sound and light alarm.
- With new type time relay, time range is more wider (1S ~ 99H).
- Using the latest current relay, more accurate and reliable.
- Light weight, small size, easy to move.
III. Specifications
A.Control unit specifications
- Power: AC220V±10%, 50Hz±1
- Capacity: 5kVA
- Output voltage: AC 0-250V
- Rated output current: 25A
- Rated current rectified range: 0-25A
- HV voltmeter range: 0-145kV
Accuracy: 1.5% of the reading±1digit(F.S)
HV ammeter range: 0-100mA
Accuracy: 1.5% of the reading±1digit(F.S)
LV ammeter range: 0-25A
Accuracy: 2.0% of the reading±5digit(F.S)
Timing range: 1s-99h
B. Testing transformer (HV unit) specifications
- Input voltage: 0-200V
- Input current: AC 0-25A
- Output voltage: AC 0-80kV, DC 0-110kV
- Output current: AC 62.5mA, DC 45.4mA
- Capacity: 5kVA
- HV side/LV side turns ratio: 400:1
- Measuring voltage: AC 0-100V
- No-load current: <4%
- Impedance voltage: <10%
C. Working conditions
- DC microammeter range: 0-2mA
- Discharge rod: 140kV
D. Working conditions
- Working place: No gas, steam, chemical dust and explosive and corrosive medium which will influence insulation.
- Environment temperature: -20--50ºC
- Environment humidity: ≤85% RH (no condensing)