GDM-16 Fault Recording & Generator Characteristic Test Set
General Information
GDM-16 Generator Characteristic Comprehensive Test System is based on the industrial portable machine structure, with high-performance DSP, high-precision ADC chip, embedded operating system as hardware and software architecture, which integrates data collection, processing, transmission, storage, analysis and other functions as one portable device.
DSP acquisition chip is used for data acquisition and calculation, so as to realize full digital analog signal filtering. Flexible and diverse sampling frequencies from 10K/s, 20K/s, 50K/s, 100k/s can be selected by users, and can be used for waveform recording and analysis of transient electrical signals.
Using advanced industrial control kernel, combined with embedded operating system, users can easily perform data storage, backup, analysis, export and other operations.
The generator characteristic comprehensive test system is a smart instrument that integrates functions such as fault recording and generator characteristic test. It is favored by the majority of users for its small size, strong function, wide application range, flexible configuration and many other advantages.
Features
Fault recording: It can monitor the working parameters in the access equipment and complete the data recording and fault data analysis during the fault;
Real-time monitoring: the device can realize analog quantity and switch quantity real-time monitoring and display functions;
Calculation amount: active power, reactive power, frequency, positive sequence, negative sequence, zero sequence, vector sum (difference) and phase angle, etc., and display the generated calculation amount in real time;
Generator total start electrical test: generator characteristic test can be completed, including generator no-load test, generator short-circuit test, main excitation no-load, load test, etc .; excitation test, including zero boost test, de-excitation test, 10% step test, etc .; simultaneous test; other tests required by the user.
This instrument can be used for online monitoring of key equipment in power systems or other industries; it can also be used as a portable instrument for monitoring and analysis of the failure of various industrial equipment; or use its data processing and calculation capabilities as a data source to providereal-time data for other system.
Specifications
1. Features of 16 analog channels Channel isolation withstand voltage: 1500VDC A/D resolution: 16 bits RMS value accuracy: 0.2% Analog sampling frequency: 10K/s, 20K/s, 50K/s, 100K/s optional There are 8 analog signal processing modules, each module is composed of 2 analog channels, and the channel configuration is as follows: AC voltage AC150V 3 channels Internal resistance> 80kΩ AC current clamp AC10A 3 channels Internal resistance <0.1Ω AC current AC10A 2 channels Internal resistance <0.1Ω AC voltage AC500V 3 channels Internal resistance> 80kΩ AC current clamp AC100A 1 channel Internal resistance <0.1Ω DC voltage DC ± 2000V 1 channel Internal resistance> 1MΩ DC voltage DC ± 32V 1 channel Internal resistance> 15kΩ DC voltage DC ± 100mV 1 channel Internal resistance> 8kΩ DC current DC4-20mA 1 channel Internal resistance 120Ω
2. Characteristics of 16-channel switch channel Switching event resolution: 0.1ms Standard configuration: 8 passive nodes and 8 active nodes (active node external voltage: DC24V-220V).
3. Failure start method Analog quantity: sudden change, excessive and insufficient quantity Switching quantity: displacement (close, open)