Type: Universal Testing Machine
Accuracy Grade: 1
Manufacturer/Factory & Trading Company

360° Virtual Tour

Diamond Member Since 2011

Suppliers with verified business licenses

Audited Supplier

Audited by an independent third-party inspection agency

Management System Certification
ISO9001:2015, ISO14001:2015, ISO 45001:2018
Export Year
2011-07-01
  • Three-phase Primary Current Injection Test Set with temperature rise test 5000A
  • Three-phase Primary Current Injection Test Set with temperature rise test 5000A
  • Three-phase Primary Current Injection Test Set with temperature rise test 5000A
  • Three-phase Primary Current Injection Test Set with temperature rise test 5000A
  • Three-phase Primary Current Injection Test Set with temperature rise test 5000A
  • Three-phase Primary Current Injection Test Set with temperature rise test 5000A
Find Similar Products

Basic Info.

Model NO.
GDSL-A-5000
Load Way
Electronic Load
Loading Method
Dynamic Load
Display
Digital
Control
Computer Control
Weight
>2000Kg
Power Source
AC220V
Max. Output current
AC Single-phase 5000A*3 groups
Circuit mode
Electric voltage regulator with special craft
Duty cycle
8 hours
AC Input Voltage
220V/ 380V , customized
Warranty
1 year
Voltage
0~12V Auto switching
Rated capacity
180kVA
Transport Package
Standard Export Wooden Box
Specification
customized
Trademark
HV Hipot
Origin
Wuhan, China
HS Code
9030899090
Production Capacity
5000set/Year

Product Description

Customized Automatic AC 3-phase Primary Current Injection Test Set 

GDSL-A-5000 Automatic 3-phase Primary Current Injection Test Set shall be applicable to current load test and temperature rise test of busbars, switchgear, circuit breakers, contactors, current transformers and other electrical equipment.


GDSL-A-5000 Automatic 3-phase Primary Current Injection Test Set with temperature rise test, uses PLC and touch screen industrial control monitor as the control system, which can realize manual and auto control. The generator can realize the output of three phase 5000A current and collect the temperature of 26 channels. It is able to display the collected temperature and current in the way of curve graph. The testing results can be exported as CSV file by U disk, which is convenient for analysis and processing on the computer. The equipment has the perfect protection and self-checking function.

Features
 
  1. Current, temperature, time, status and prompt information and other data will display on large LCD screen, the reading is clear and intuitive;
  2. Full English interface, touch screen operation, operation is simple and clear, can be adapted to a variety of applications;
  3. Direct viewing operation, not only can operate by panel button, but also can operate by touch screen, quick and easy to handle.
  4. When set up into auto current boosting, the three-phase output current is automatically adjusted and balanced, and the precision is easy to control.
  5. Status alert function, guided operation, the user can skilled manipulation even in the case of no manual;
  6. Pause function, during automatic control, it can achieve pause at any point of current rise/drop process, pause time can be controlled by the test personnel, convenient to observe the state of the test objects.
  7. Test time can be arbitrarily set, 0 second to 20 hours;
  8. Timing function, whether it is in automatic control or manual control, the timer will be started by manually, when the time is up, display the test results, the device automatically back to zero;
  9. Manual control mode, this mode is similar to the traditional electric rise/drop mode, current increase/decrease is controlled by press-button, equipment will automatically determine the upper/lower limit, with over-current protection, manual control of the whole test procedure, on-demand operation.
  10. The panel has an emergency button. When the equipment is abnormal, the control power can be cut off quickly.
  11. When the ambient temperature and the internal temperature of equipment are high, please open the fan switch on the panel to do heat dissipation for equipment.
  12. For different loads, manual reactive power compensation can be realized.
  13. When over-current and other the faults occurs, the protection of real-time, accurate and reliable;
  14. Using hardware and software anti-interference technology, stable performance, strong anti-interference ability, the abnormal phenomenon of crashes, black screen and blurred screen does not appear in the test.
  15. The equipment is equipped with a hardware self checking function, which can identify the fault of the screen control broken line, the internal parameter register fault and the output current collector fault.
 
Specifications
 
Type GDSL-A-5000
Max. Output current AC Single-phase 5000A*3 groups
Circuit mode Electric voltage regulator with special craft
Duty cycle 8 hours
AC Input Phase line 3P
Voltage 208V±10%, 60Hz±2% 3Φ4W
Input current 288A   
Output Phase line 3Φ4W
Voltage 0~12V Auto switching
Current AC0~5000A continuous adjustable, stepless speed regulation;
3-phase can output at one time, can output single-phase, also can split phase output;
Tow kinds of output-manual mode and auto mode;
Rated capacity 180kVA
Stabilized current accuracy Output current≤±0.5%
Output terminal Wiring terminal
Protection The electronic circuit rapidly detects over voltage, over current, over temperature, phase loss, etc., automatic tripping protection and alarm device, the voltage and the current is zero in non-test status.
Accuracy Source effect 0.3% of rated value
Time drift 1% of rated value
Temp. drift 0.04% of rated value/°C
Load effect 1% of rated value (Output voltage change rate due to the output current change from zero to the rated value.)
Ripple voltage 1% of rated value+10mV
Others Line regulation 0.1%
Load regulation 0.1%
Display and settings Voltage meter display True color LCD and digital display instrument (display accuracy: 0.1V display error: ≤1.03 digit)
Current meter display True color LCD and digital display instrument (5 digits display, display accuracy: 0.1A display error: ≤1.03 digit)
Adjustment setting Current (High precision potentiometer adjustment)
System Efficiency ≥90%
Resistance Withstand voltage insulation resistance AC1800V 1min, 20MW
Cooling device Forced fan cooling
Noise <60dB (1mm in front of the device)
CT accuracy 0.2%
Protection level IP20
Working environment Working mode Long time temperature rise test
Temperature -10°C~50°C
Humidity 0-90% (non-condensing)
Altitude <1500m
Appearance Structure Integration
  Dimension Customized
  Weight Approx. 2.5T
Temperature inspection 26-way module  
A class thermocouple PT100 with 6m line * 26pcs

It is customized , feel free to contact us with your requirements .

Three-phase Primary Current Injection Test Set with temperature rise test 5000A
Three-phase Primary Current Injection Test Set with temperature rise test 5000A
Three-phase Primary Current Injection Test Set with temperature rise test 5000A
Three-phase Primary Current Injection Test Set with temperature rise test 5000A
 

Send your message to this supplier

*From:
*To:
*Message:

Enter between 20 to 4,000 characters.

This is not what you are looking for? Post a Sourcing Request Now
Contact Supplier