GDYT-10/100 Partial Discharge Test System 10kVA/100kVAC GDYT-10/100 Partial Discharge Test System is mainly used for testing frequency voltage insulation level of various insulation materials, insulation structure and electrical products, also as partial discharge frequency testing power supply for testing objects such as transformers,mutual inductor and lightning arresters.It is widely used in electrical manufacturing,power operation departments, research institutes and universities.
The system includes,
Hipot Test Control Table GDYD-10/100
PD-free Gas type transformer YDQW-10/100
Coupling capacitor TAWF-800PF/100kV
Protective resistor GR100kV
Isolation filter LBQ-10kVA
Partial discharge analyzer GDJF-2008
Product Parameters
System Specifications
Power supply: 230V±10%, 50Hz
Rated Capacity: 10kVA
Output Voltage: 100kV, current: 100mA
Short-circuit impedance: <18%
Operation time: 30mins@100% rated voltage and current.
Continuous working @ 2/3 rated voltage and current.
Wave form distortion rate:<3% when voltage regulator input voltage distortion rate <3%.
PD value: ≤5pC @ 100% rated voltage
1. Control unit
Features
Digital display meters mounted on the panel.
MonitoringHV side voltage, HV side current, LV side current and indicator of zero,power, working start,timing.
Over-current protection,zero-starting protection, sound and light alarm.
Withthe new type time relay,time rangeis wider (1S ~ 99H).
Using the latest current relay, more accurate and reliable.
With wheels for both control unit and HV unit, easy to move.
Specifications
Power: AC230V±10%, 50Hz
Capacity: 10kVA
Output voltage: AC 0-250V
Rated output current: 50A
Rated current rectified range:15-50A
HV voltmeter range: 0-100kV
Accuracy: 1.5% of the reading±1digit(F.S)
HV ammeter range:0-100mA
Accuracy: 1.5% of the reading±1digit(F.S)
LV ammeter range: 0-50A
Accuracy: 2.0% of the reading±1digit(F.S)
Timing range:1s-99h
Weight: 40kg
Dimension: 460mm (L)*360mm (W)*510mm (H)
2. PD-free Gas testing transformer (HV unit)
Rated capacity: 10kVA
Input voltage: 0-200V
Input current: AC 0-50A
Output voltage: AC 0-100kV
Output current: AC 100mA
Voltage accuracy: AC 1.5%
PC value on rated voltage: ≤5pc
Voltage distortion factor: <3%
Insulation dielectric: SF6 gas
Weight: about 87kg.
Coupling capacitor
Rated frequency: 50Hz
Standard capacitance: 800pF±10%
Rated voltage: 100kV
Voltage ratio: 1000/1
Dielectric loss: <0.5%
Measurement accuracy: 1%
Permitted operation time: same with testing transformer
PD value: ≤5pc on 100% of rated voltage, ≤3pc on 80% of rated voltage.
Protective resistor
Rated frequency: 60Hz
Rated voltage: 100kV
Resistance: 5.69k
Rated current: 0.1A
Permitted operation time: same with testing transformer
5. Isolation filter LBQ-10kVA
With L-C filter loop circuit, and built-in filter compensation device
Rated capacity: 10kVA
Rated voltage: 200V
Rated current: 50A
Frequency: 50Hz
Attenuation: 40kHz-100kHz ≥40dB
100kHz-1.5Mhz ≥60dB
Permitted operation time: same with testing transformer