GDYD-1510A 10kVA.150kV Automatic AC Hipot Test Set With Oil Type Testing Transformer

GDYD-1510A Automatic AC Hipot Test Set is composed of automatic control unit and AC oil type testing transformer (HV unit) which output AC voltage smoothly. Meanwhile, it has many monitoring and protection functions.
Features
- 7inch color LCD screen, with PLC automation control.
- HV Voltage, LV voltage, LV current measured at the same time, with high precision sensor and high-performance collection chip.
- Automatic mode and manual mode for option.
- Display HV voltage, LV voltage, LV current, time, and withstanding result.
- Over-voltage and over-current protection. Output voltage, HV current upper limit, LV current upper limit and timing can be set.
- Support stage voltage increasing, total 3stages, each stage voltage can be set, which is convenient to find object problem.
- Support automatic control of increasing speed, total 6ranges to be selected, 0.5kV/s, 1kV/s, 1.5kV/s, 2kV/s, 2.5kV/s, 3kV/s.
- Zero-starting function. Test can be proceeded after the voltage is back to zero.
- Store up to 8000pcs data in 3months. It has USB port to upload data to USB disk.
- When setting voltage is arrived, it will be timing automatically. After timing, voltage will be back to zero.
- When the LV current is over setting value, the voltage will be cut off automatically and it will be back to zero. When the HV current is over setting value, the test object will be cut off and test can be proceeded continuously.
- With anti-interference ability, suitable for electromagnetic environment.
- With wheels for both control unit and HV unit, easy to move.
Specifications
A.Control unit specifications
- Power: AC220V, 50Hz
- Capacity: 10kVA
- Output voltage: AC 0-250V
- Rated output current: 50A
- Rated current rectified range: 0-50A
- HV voltmeter range: 0-150kV
- Accuracy: 2.0% of the reading±1digit (F.S)
- HV ammeter range: 0-67mA
- Accuracy: 2.0% of the reading±1digit (F.S)
- LV ammeter range: 0-50A
- Accuracy: 2.0% of the reading±1digit (F.S)
- Timing range: 1s-99h
- Weight: about 75kg
- Dimension: 570mm (L)*530mm (W)*1040mm (H)
B. Testing transformer (HV unit) specifications
- Input voltage: 0-200V
- Input current: AC 0-50A
- Output voltage: AC 0-150kV
- Output current: AC 66.6mA
- Capacity: 10kVA
- HV side/LV side turns ratio: 750:1
- Measuring voltage: AC 0-100V
- Accuracy: 2.0% of the reading±1 digit (F.S)
- No-load current: <10%
- Impedance voltage: <10%
- Weight: about 180kg
- Dimension: 580mm(L)*440mm(W)*1280mm(H)
C. Working conditions
- Working place: No gas, steam, chemical dust, and explosive and corrosive medium which will influence insulation.
- Environment temperature: -20--50ºC
- Environment humidity: ≤85% RH (no condensing)
Accessories
Control Unit 1set
Oil type testing transformer (HV unit) 1set
Power cord 1 piece
Metering cable 1 piece
Output cable 1 piece
HV cable 1 piece
Ground cable 1 piece
User's guide 1 piece
Factory test report 1 piece