HV HIPOT Multi Phase Relay Protection Testing Solution System

Product Details
Customization: Available
After-sales Service: Yes
Warranty: 1 year
Manufacturer/Factory & Trading Company

360° Virtual Tour

Secured Trading Service
Diamond Member Since 2011

Suppliers with verified business licenses

Audited Supplier Audited Supplier

Audited by an independent third-party inspection agency

Year of Establishment
2006-11-08
Number of Employees
68
  • HV HIPOT Multi Phase Relay Protection Testing Solution System
  • HV HIPOT Multi Phase Relay Protection Testing Solution System
  • HV HIPOT Multi Phase Relay Protection Testing Solution System
  • HV HIPOT Multi Phase Relay Protection Testing Solution System
  • HV HIPOT Multi Phase Relay Protection Testing Solution System
Find Similar Products
  • Overview
  • Product Description
  • Product Parameters
  • Company Profile
Overview

Basic Info.

Model NO.
RPT-4632B
Power Supply
AC 220V; 50Hz
Weight
19KG
Size
480mm*360mm*2000mm
AC Current output range
6*0-30A phase, 3* 0-60A phase
DC Current Output range
6*0-10A phase, 3*0-20A phase
AC Voltage Output range
4*300V phase
DC Voltage Output range
4*400V phase
Binary Input Number
8 pairs
Binary Output Number
4 pairs
Transport Package
Carton or Wooden Case
Specification
ISO, SGS
Trademark
HV Hipot
Origin
Wuhan China
HS Code
9030820000
Production Capacity
2000PCS/Year

Product Description

 RPT-4632B Relay Protection Tester

Product Description

RPT-4632B relay protection tester is a high-performance microcontroller based control unit developed and produced by HVHIPOT company, specifically designed for comprehensive testing and verification scenarios of power system relay protection devices. Adopting a modular architecture combined with high-precision current and voltage amplifiers to improve output accuracy and stability, with panoramic coverage of functions suitable for multiple testing scenarios. Equipped with the advanced algorithm of the Smart Quick Intelligent Testing System (Soft Writing Registration No. 1010215), it accurately analyzes test data and provides efficient and precise technical support. The equipment integrates conventional relay protection testing, digital relay protection testing, mixed signal relay protection testing, merged unit testing, intelligent terminal testing, message analysis and measurement, SCD file parsing and comparison, MMS related services, and cloud testing functions, which can fully meet the testing requirements of all types of relay protection and automatic devices in power plants, conventional substations, intelligent substations, and new generation substations.



Applicable Standards

DL/T 860 Series Standard "Substation communication network and system"
DL/T 624-2010 "Technical specifications of test equipment based on micro-computer for protection equipment"
GBT 7261-2008 "Basic testing method for replaying protection and security automatic equipment"
IEC 60255-24:2001 "Electrical relays - Part 24: Common format for transient data exchange (COMTRADE) for power systems"


Features
 

  1. Supports 6-phase 30A or 3-phase 60A current output and 4-phase 300V voltage output, meeting heavy load requirements.
  2. A hybrid digital-analog output architecture enables analog and GOOSE protection device testing, ensuring timing consistency.
  3. Equipped with an embedded Linux operating system, it ensures stable system operation.
  4. Features high-performance SV and GOOSE message analysis capabilities, delivering accurate parsing and excellent processing efficiency.
  5. Integrated SCD file comparison and graphical display enhance file processing efficiency and intuitiveness.
  6. Equipped with optical power measurement, it expands device application scenarios in multiple dimensions.
  7. Supports online reading and verification of CID model files, enabling one-click consistency verification between the device's internal CID file and the SCD file, improving configuration verification efficiency.
  8. Equipped with cross-platform application software, it supports both on-site touchscreen operation and computer-connected operation, adapting to different debugging habits.
  9. Built-in cloud testing functionality leverages cloud server technology to download and access test templates and cases.
  10. One-click automatic test start precisely meets the standardized testing requirements of factory commissioning of protection devices.
  11. Supports reading and verification of protection settings, pressure plate information, and other information, efficiently completing on-site timing verification.
  12. The current and voltage output accuracy reaches 0.05%, accurately meeting the testing requirements of the merging unit.
  13. Configure a gigabit interface to efficiently meet the needs of gigabit message transmission and reception.
  14. Integrate data serial forwarding function to improve data exchange efficiency.
  15. Built in GPS/Beidou to optical B-code function, providing high-precision clock synchronization service as a standard B-code source.
  16. Adopting a 9-inch high-definition capacitive touch screen, it combines high-definition display and precise touch control.
  17. Built in WiFi, Bluetooth, and 4G IoT communication capabilities, building multi-dimensional wireless communication capabilities.
  18. Built in abnormal working condition alarm mechanism, real-time monitoring of various faults such as voltage source short circuit, current source open circuit, equipment overheating, and signal distortion, and quickly triggering alarm response.
  19. Support automatic upgrade of systems and software via USB flash drive, and PDF and CSV format reports can be copied and archived through USB flash drive for data traceability management.
Product Parameters

Specifications

 
Function Options Technical Parameters
AC Current settings Each phase output current amplitude, frequency and phase are independently adjustable
Output range 6 x 0-30A/phase or 3 x 0-60A/phase
Accuracy Typical: <±0.2mA (0A-0.2A)
<±0.05%±0.1mA (0.2A-10A)
<±0.1% (10A-20A)
<±0.2% (20A-Imax)
Guaranteed: <0.08% rd + 0.02% rg, at (0-20A)
<0.15% rd + 0.05% RG at(20A to Imax)
Resolution 1mA
Current rise and fall time <100µs
Max. output power Pmax 30A/phase110VA/phase, 60A/phase≥180VA/phase
Total harmonic distortion (THD%) Typical value: ≤0.1% (2A to Imax), ≤0.2% (0.2A to 2A)
Guaranteed value: ≤0.5% (0.5A to Imax)
Frequency 10Hz ~1kHz
Amplitude-frequency characteristics Amplitude variation: ≤±0.05% to ±0.5% (10Hz to 1kHz)
Output time <5A/phase, continuous output
Abnormal operating condition alarm Automatic detection and alarm for overheating, overload, distortion, and open circuit
DC Current Output range 6×0~10A/phase, 3×0~20A/phase
Accuracy Typical value: <±1mA (0A to 0.2A); ±0.5% (0.2A to Imax)
Guaranteed value: ±5mA at (0A to 0.2A); 0.3%rd + 0.2%rg at (0.2A to Imax)
Resolution 1mA
AC Voltage Settings Each phase output voltage amplitude, frequency and phase are independently adjustable
Output range 4×300V/phase
Accuracy Typical value: <±1mV (0V-2V)
<±0.05% (2V-Vmax)
Guaranteed value: <0.08%rd + 0.02%rg (0-Vmax)
Resolution 1 mV (0.2V-10V), 10 mV (10V-300V)
Max. output power (Pmax) 4×300V/phase≥90VA/phase
Voltage rise and fall time <100µs
Total harmonic distortion (THD%) Typical value: ≤0.1% (2V to Vmax)
Guaranteed value: ≤0.2% (2V to Vmax)
Frequency 10Hz~1kHz
Amplitude-frequency characteristics Amplitude variation ≤±0.05% to ±0.5% (10Hz to 1kHz)
Output time Continuous output under rated conditions
Abnormal operating condition alarm Automatic detection and alarm for overheating, overload, distortion, and short circuits
Current and voltage synchronization error ≤10µs
DC Voltage Output range 4×400V/phase
Accuracy Typical value: <±4mV (0V-2V), ±0.2% (2V-Vmax)
Guaranteed value: ±5mV (0V-2V); <0.3%rd + 0.2%rg, at (2V-Vmax)
Resolution 1mV (0.2V-10V), 10mV (10V-400V)
Binary Input Number 8 pairs
Input characteristics 8 pairs of open input contacts adapt to empty or charged contacts.
1-4 charged contacts have a switching level of 20-250V (DC).
5-8 charged contacts have a switching level of 9-28V (DC).
Electrical isolation All 8 pairs of open input contacts are electrically isolated.
No-contact threshold impedance parameters 3kΩ~5kΩ
Binary Output Number 4 pairs
Type Conventional contacts (response time <2ms)
Fast-acting contacts (response time <100μs)
DC capacity Vmax: 300V (DC) / Imax: 0.3A (excluding fast-acting contacts)
Frequency Sine signal 10Hz~1000Hz
Accuracy <1mHz (45Hz-65Hz)
<5mHz (10Hz-45Hz, 65Hz-450Hz)
<10mHz (450Hz-1000Hz)
Resolution 0.001Hz
Output characteristics Can superimpose 2nd-21st harmonics of any amplitude (less than the rated value)
Phase Phase angle range 0 - 359.9°
Accuracy Typical value: ≤±0.1°
Guaranteed value: ≤±0.2°
Resolution 0.01°
Small Signal Analog Output Number of channels 8-channel
Output range 0 to 7.07 Vrms (RMS)
Accuracy Typical: <±0.1 mV (0 V to 0.1 Vrms); ±0.05% (0.1 Vrms to 7.07 Vrms)
Guaranteed: < 0.03% rd + 0.02% rg, at 0 V to 7.07 Vrms
Max. output current 1mA
Harmonic distortion <0.05%
Auxiliary Dc Power Output (Optional) Number of channels 1 group
Output range DC 110V/220V switchable
Max. output power Pmax 85W (110V), 170W (220V)
Fiber Optic Ethernet Interface
 
Number 8 pairs, including one pair for Gigabit networks
Interface type LC interface
Wavelength 100M port: 1310nm, Gigabit port: 850nm
Communication protocol IEC61850-9-2, GOOSE, IEC1588
Fiber Optic Serial Interface Number 4 ports, 2 transmit, 2 receive
Interface type ST interface
Wavelength 820nm
Communication protocol IEC60044-8, IRIG-B, PPS
Electrical Ethernet Interface Number 2 ports
Interface type RJ45
Communication protocol MMS, TCP/IP
Bluetooth Port Number 1
Wi-Fi Port Number 1
Usb Port Number 1
4G Port (Optional) Number 1
Synchronous Interface GPS/Beidou interface Built-in GPS/Beidou chip, supports GPS or Beidou timing.
Optical B-code transmission 2 ST interfaces, multiplexed with the FT3 port.
Optical B-code reception 1 ST interface, multiplexed with the FT3 port.
PPS pulse reception 1 ST interface, multiplexed with the FT3 port.
I588 timing interface 1 pair of LC , multiplexed with the optical network port.


Others




 
Battery Built-in large-capacity lithium battery pack
Power adapter Input: AC 100-240V, 50/60Hz, 2A
Output: DC 8.4V, 5A
Rated voltage 220V (AC)
Permitted voltage 176V~253V (AC)
Rated frequency 50Hz
Permitted frequency 40~60Hz
Current 6A(max)
Display 9-inch capacitive LCD screen (touch screen)
Dimension 315mm×240mm×140mm (W×H×D)
Weight <8kg

Company Profile

HV HIPOT Multi Phase Relay Protection Testing Solution SystemHV HIPOT Multi Phase Relay Protection Testing Solution SystemHV HIPOT Multi Phase Relay Protection Testing Solution SystemHV HIPOT Multi Phase Relay Protection Testing Solution System

 

Send your message to this supplier

*From:
*To:
*Message:

Enter between 20 to 4,000 characters.

This is not what you are looking for? Post a Sourcing Request Now
Send Inquiry
Chat Now