• HVHIPOT AC/DC Hipot Test Set (GDYD-55C) Dielectric Strength Test
  • HVHIPOT AC/DC Hipot Test Set (GDYD-55C) Dielectric Strength Test
  • HVHIPOT AC/DC Hipot Test Set (GDYD-55C) Dielectric Strength Test
  • HVHIPOT AC/DC Hipot Test Set (GDYD-55C) Dielectric Strength Test
  • HVHIPOT AC/DC Hipot Test Set (GDYD-55C) Dielectric Strength Test

HVHIPOT AC/DC Hipot Test Set (GDYD-55C) Dielectric Strength Test

Application: Power, Electronic
Phase: Single
Core: Core-type Transformer
Cooling Method: Oil-immersed Type Transformer
Winding Type: Separated Winding Transformer
Certification: ISO9001-2000, ISO9001
Customization:

360° Virtual Tour

Diamond Member Since 2011

Suppliers with verified business licenses

Manufacturer/Factory & Trading Company

Basic Info.

Model NO.
GDYD-55C
Usage
Testing Transformer
Frequency Characteristics
Power Frequency
Brand
HV Hipot
Input
AC240V, 50Hz
Frequency
50Hz ± 1
Output Voltage
1: AC 0-50kV; DC 0-70kV 2: AC 0-100kV (in series)
Output Current
1: AC 100mA; DC 0-71.4mA 2: AC 0-100mA (in series)
Capacity
5kVA
Current accuracy
≤ 1.5% (F.S)
Delivery time
15-45days
Transport Package
Wooden Case
Specification
ISO, SGS
Trademark
HV Hipot
Origin
Wuhan China
HS Code
8504210000
Production Capacity
1000 Pieces/Year

Product Description

I. General information

GDYD series AC hipot test set is composed of manual control unit and AC/DC Dry testing transformer(HV unit) which output AC/DC voltage smoothly. Meanwhile, it has many monitoring and protection functions.

 

II. Features

Digital display meters mounted on the panel.

Monitoring HV side voltage, HV side current, LV side current and indicator of zero, power, working start, timing.

Over-current protection, zero-starting protection,sound and light alarm.

With new type time relay, time range is wider (1S ~ 99H).

Using the latest current relay, more accurate and reliable.

Light weight, small size, easy to move.

 

III. Specifications
 

Testing transformer (HV unit) specifications
LV side voltage (Input voltage) 0-200V
LV side current (Input current) AC 0-25A
Output voltage 1: AC 0-50kV; DC 0-70kV 2: AC 0-100kV (in series)
Output current 1: AC 100mA; DC 0-71.4mA 2: AC 0- 50mA (In series)
Capacity 5kVA
HV side/LV side turns ratio 250:1
Measuring voltage AC 0-100V
Accuracy 1.5% of the reading±1 digit(F.S)
No-load current <10%
Impedance voltage <10%
Control unit specifications
Power AC240V, 50Hz
Capacity 5kVA
Output voltage AC 0-250V 
Rated output current 25A
Rated current rectified range 0-25A
HV voltmeter range AC 0-50kV,  AC 0-100kV
Accuracy 1.5% of the reading±1digit(F.S)
HV ammeter range  AC 0-100mA,  AC 0-50mA
Accuracy 1.5% of the reading±1 digit(F.S)
Timing range 1s-99h
Weight 17kg
Dimension 440mm (L)*340mm (W)*240mm (H)

Send your message to this supplier

*From:
*To:
*Message:

Enter between 20 to 4,000 characters.

This is not what you are looking for? Post a Sourcing Request Now