Customization: | Available |
---|---|
Type: | CT/PT analyzer |
Accuracy Grade: | 1 |
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
General introduction
GDHG-103 CT/PT Calibrator is mainly used to calibrate CT/PT with accuracy class 0.01 to class 10, CT secondary rated current is 5A, 1A and PT secondary rated voltage is 100V, 100/3V, 150V(100/3V,220V). The test result is shown directly by figure.
Features
Optional components:
Specifications
Measurement Range |
In-phase component(%): 0.0001-200, resolution 0.0001 |
Quadrature component(min): 0.001-700.0, resolution 0.001 |
|
Impedance(Ω): 0.001-20.0, resolution 0.0001 |
|
Admittance(ms): 0.0001-20.0, resolution 0.0001 |
|
Accuracy |
Basic error |
In-phase component: ΔX=±(X×2%+Y×2%)±Dx |
|
Quadrature component: ΔY=±(X×2%+Y×2%×34.48)±Dy |
|
X,Y-- Display value of instrument |
|
Dx, Dy-- Quantization error |
|
lError of Percent table: 1.5% (1.0% for option) |