Customization: | Available |
---|---|
Type: | Test and Measurement Instruments |
Detectable Voltage Range: | 10V-500kV |
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
1.1 General Purpose
The "Wireless Phase Detector" is mainly used in electric power lines, substation phase and phase sequence calibration, with main functions including electrical inspection, phase calibration and phase sequence measurement and so on. This product adopts double shielding and entirely new digital circuits, with strong anti-interference, in full accordance with (EMC) standards, adapted to various electromagnetic interference situations.
The high voltage phase signal of measured lead will be launched out directly after treatment, the handset will receive and make phase comparison, determine the results after the phase calibration, real-time display phase angle difference and vector.
This product uses wireless transmission technology, thereby achieving safe and reliable, fast and accurate, different voltage levels (10V-500KV) are all applicable. When checking the grid structure, enable to accurately identify the relative phase of the different leads for the three-phase connected line, without any electrical connection between two measurement components, it makes the application of the measurement device is very flexible and safe.
1.2 Security Matters
Note: The safe usage length and test standards of insulating rod for "Wireless Phase Detector". (Excerpting from "Electrical safety working regulations of State Grid Corporation".)
1. Safety distance between staff and the charged body during live operation.
Voltage Level | 10kV | 35kV | 66kV | 110kV | 220kV | 330kV | 500kV |
Safety Distance | 0.4M | 0.6M | 0.7M | 1.0M | 1.8M | 2.2M | 3.4M |
Voltage Level | 10kV | 35kV | 66kV | 110kV | 220kV | 330kV | 500kV |
Minimum effective insulation length | 0.7M | 0.9M | 1.0M | 1.3M | 2.1M | 3.1M | 4.0M |
Test voltage | 10V-500kV, different voltage level are applicable |
Accuracy | Self-calibrating ≤±3° |
Sampling speed | 10 times/s |
Date and time settings | Adjusting date and time, make it easy for users to browse, view the historical data |
Back-light time settings | Normally on, normally off, 0-999s can be set by user self |
Auto power off settings | 0-999s can be set by user self |
In-phase qualitative | ≤20° as in-phase (phase threshold within 0-90°, can be set by user self. The system default is 20°.) |
Out-phase qualitative | >20° ((phase threshold within 0-90°, can be set by user self. The system default is 20°.) |
Field calibration function | enable to carry out on-site calibration for measured lead, ensure the accuracy of phase angle |
Transmission distance between handset and X, Y detector | X≤150m, Y≤150m |
Multiple model design, with strong applicability, more safe and convenient | |
Unique human-computer interaction interface, simple operation; | |
FCC antenna design, the signal is stronger and easier to penetrate the blocking of wall, door or barrier; | |
Double shielding, strong an-ti interference, in full accordance with EMC standards; | |
Charts and data display, more convenient and easy to read; | |
Qualitative measurement: | Display by sound and light signal; |
Quantitative measurement | Real-time display phase angle difference, error≤5°; |
Phase sequence calibration | Positive phase sequence, negative phase sequence (120°, 240°); |