| Customization: | Available |
|---|---|
| Type: | Universal Testing Machine |
| Load Way: | Electronic Load |
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
| Power supply | Supporting external power adapter (12V/2A) and internal battery power supply mode |
| Measurement range | Leakage current(peak value) : 0~ 10mA (Extensible) Voltage(peak value) : 30-100V(Extensible) |
| Measurement accuracy | Current: ±2% reading±1 digital at full current> 100 μA Voltage:±5% reading +1 digital at reference voltage signal< 30V: Voltage: Reference voltage signal > 30V: Wire mode: +2% reading +1 digital; Wireless mode: +5% reading +1 digital; |
| Measurement parameters | Full current waveform, fundamental RMS and peak value of leakage current. The fundamental wave RMS of leakage current resistive component and RMS of 3, 5 and 7 times. Leakage current resistance component peak value: positive peak Ir + negative peak Ir-. Capacitive current fundamental wave, full voltage, full current phase angle difference. Voltage RMS. Arrester power consumption. |
| Sampling method of voltage reference signal: | Wire Synchronization: 40m (Extensible) Wireless Synchronization: > 400m (Extensible) |
| Battery | Charging time: > 6 hours Continuously working time: > 4hours Interval working time:> 8 hours |
| Dimension | Main unit: 36cm*26cm*14cm Accessories Box: 42cm*33cm*20cm |
| Weight | Main unit: 5.0kg , Accessories box : 9.0kg |