GDKC-15A Circuit Breaker Analyzer
Product Description
High voltage circuit breaker is one of the most important control equipment in the power system. GDKC-15A is used to test the dynamic characteristics of high voltage circuit breaker. It is easy to operate, with high accuracy.
Features
- It is suitable for the mechanical test of all types of SF6 switches, GIS combination appliances, vacuum switches and oil switches.
- Strong anti-interference ability. It can be easily tested and accurately measured in 500kV substation.
- Accelerometer (optional), linear sensor, rotary sensor, easy to install and simple.
- When the switch is actuated once, all the data of the switch mechanical characteristic test and the corresponding waveform map are obtained.
- Store the field test data and built-in real time clock, which is convenient for archiving and saving the test date and time.
- With 8inch LCD screen, display all data and map, with background light, LCD contrast adjustment and power off memory.
- Friendly menu operation, easy to use. With built-in printer to quickly print all data results.
- Equipped with data analysis management software, which can be operated online with PC, with WORD format file. The test results can be output to all kinds of printers printing test reports to make the field test computerized.
- Combined speed selection and user-defined function set according to needs, suitable for the speed measurement of any type of switches.
Performance
Performance
1. Time:
12 contacts inherent open (close) time
Open (close) in phase different period
Open(close) phase-to-phase different period
2. Reclosing:
C-O, O-C, C-O-C time,
One combined time, two combined time, short time, no current time value.
3. Bouncing:
The bounce time of each contact, the number of bounces, the bounce process, the bounce waveform.
The amplitude of the rebound of each contact.
4. Speed: just open, just cloase speed, maximum speed, time-travel characteristic curve.
5. Travel: total travel, open distance, over travel, overshoot trip, rebound amplitude.
6. Current: the open and close current value and current waveform of open/close coils.
7. Operating voltage
DC0-300V/20A digital adjustable circuit breaker operating power supply is provided in the machine, and the power is automatically completed.
The low voltage operation test measures the operating voltage value of the circuit breaker.
8. Static resistance: 100A contact resistance measurement.
9. Dynamic resistance (Pre-insertion resistor): 100A change waveform of dynamic resistance during circuit breaker operation.
Specifications
Usage Environment
Input Power: 220V±10%, 50Hz±10%, Air Pressure: 86-106kpa
Temperature: -10-40ºC Humidity: ≤80%RH
Safety Performance
Insulation Resistance>2MΩ
Dielectric Strength: Shell can withstand power frequency voltage 1.5kV at 1 minute without flashover and arcing.
The Basic Parameters
Time: Range 20000.0ms, resolution 0.01ms
Error 0.01ms ± 2digit within 200ms
0.1ms ± 2digit within 2000ms
1ms±2 digit within 20000ms
Static resistance: range 10mΩ, minimum resolution 0.01uΩ
Dynamic resistance: range 10mΩ, minimum resolution 1uΩ
Velocity: Range 20.00m/s resolution 0.01m/s
Error ±0.1m/s± 1digit within 0-2m/s
±0.2m/s± 1digit above 2m/s
Travel:
Types |
Range |
Resolution |
Error |
Vacuum breaker |
50.0mm |
0.1mm |
0.1±1mm |
SF6 circuit breaker |
300.0mm |
1mm |
Oil circuit breaker |
600.0mm |
Current: range 20.00A, resolution 0.01A
Output power: DC 0-300V digital adjustable/20A (instantaneous working), resolution 1V.
Dimensions: about 570mm (L)* 400mm (W)* 240mm (H)