GDYT-5/10 Partial Discharge Test System 5kVA/10kV AC
General information
GDYT-5/10 Partial Discharge Test System is mainly used for testing frequency voltage insulation level of various insulation materials, insulation structure and electrical products, also as partial discharge frequency testing power supply for testing object such as transformer,mutual inductor and lightning arresters.It is widely used in electrical manufacturing,power operation departments, research institutes and universities.
The system includes,
Automatic Hipot Test Control Table GDYT-5kVA/10kV
PD-free Gas type transformer YDQW-5kVA/10kV
Coupling capacitor TAWF-5/800pF
Protective resistor GR-5kVA
Isolation filter LBQ-5kVA/200V
Partial discharge detector GDJF-2008 optional
II. System principle diagram
K1: Circuit breaker TY: Voltage regulator GK: Compensation reactor LBQ: Anti-interference filter TPU: Fast Over-voltage protection device(Optional) B1: Testing transformer R: Protective resistor KZ: Control table C1&C2: Capacitive divider with Coupling capacitor
III. System Specifications
Specifications
System Specifications
Power supply: 220V±10%,50HZ
Rated Capacity: 5kVA
Output Voltage: 10kV, current: 500mA
Short-circuit impedance: <18%
Operation time: 30mins@100% rated voltage and current.
Continuous working@ 2/3 rated voltage and current.
Wave form distortion rate:<3% when voltage regulator input voltage distortion rate <3%.
PD value:≤5pC @ 100% rated voltage
1. Control unit GDYD-5kVA/10kV
Features
7inch color LCD screen, with PLC automation control.
HV Voltage, LV voltage, LC current measured at the same time, with high precision sensor and high-performance collection chip
Automatic mode and manual mode for option.
Display HV voltage, LV voltage, LV current, time and withstanding result.
Over-voltage and over-current protection. Output voltage, HV current upper limit, LV current upper limit, and timing can be set.
Zero-starting function. The test can proceed after the voltage is back to zero.
Store up to 8000pcs data in 3months. It has a USB port to upload data to a USB disk.
When the setting voltage arrives, it will timing automatically. After timing, the voltage will be back to zero.
When the LV current is over-setting value, the voltage will be cut off automatically and it will be back to zero. When the HV current is over-setting value, the test object will be cut off and test can proceed continuously.
With anti-interference ability, suitable for the electromagnetic environment.
With wheels for both the control unit and HV unit,easy to move.
Specifications
Power: AC220V±10%, 50Hz±1
Capacity: 5kVA
Output voltage: AC 0-250V
Rated output current: Max. 25A, resolution 0.1A
HV voltmeter range:0-10kV AC, resolution 0.01kV
HV current measurement range: 0-500mA, resolution: 1mA
Timing range: 0-999s
Voltage and current accuracy: ≤3%(F.S)±2digits
Environment temperature: -20ºC to 50ºC
2. PD-free Gas testing transformer (HV unit) YDQW-5kVA/10kV
Rated capacity: 5kVA
Input voltage: AC 220V±10%
Input current: AC 0-250A
Output voltage: AC 0-10kV
Output current: AC 0-500mA
Measurement ratio: 100:1, error ±1%
Impedance: ≤12%
No-load current: ≤10%
PC value on rated voltage: ≤5pc
Voltage distortion factor: <3%
Insulation dielectric: SF6 gas
Dimensions & Weight: 360mm*360mm*600mm, 38kG
Coupling capacitor TAWF-5/800
Rated frequency: 50Hz
Standard capacitance: 800pF±10%
Rated voltage: 10kV
Voltage ratio: 500/1
Dielectric loss: <0.5%
Measurement accuracy: 1%
Permitted operation time: same with testing transformer
PD value: ≤5pc on 100% of rated voltage, ≤3pc on 80% of rated voltage.
Structure type: insulating shell oil-paper capacitor structure: composed of the top cover, voltage-equalizing ring, capacitor body, mobile base, low voltage arm, etc.
Protective resistor GR-5
Rated frequency: 50Hz
Rated voltage: 10kV
Resistance: 5kOhm
Rated current: 0.5A
Permitted operation time: same with testing transformer
Temperature rise: H class (135ºC)
Partial discharge: ≤3pC at 100% rated voltage
≤2pC under 80% rated voltage
Structure type: The resistor is wound with an enameled resistance wire on an epoxy resin board, and adopts a honeycomb structure, so that the heat emitted by the heating wire can be fully exchanged with the air, reducing the temperature of the resistor when it is in use, and ensuring that the strength of the resistance parent material does not decrease when heated. Both ends are connected to the transformer and the voltage divider with connecting pipes.
Isolation filter LBQ-5
With L-C filter loop circuit, and built-in filter compensation device
Rated capacity: 5kVA
Rated voltage: 220V±10%
Rated current: 25A
Impedance: ≤12%
No-load current: ≤10%
Frequency: 50Hz
Attenuation: 10kHz-100kHz ≥20dB
100kHz-30Mhz ≥60dB
Permitted operation time: same with testing transformer